101S Protocol Configuration

IEC-101 Slave ♦ ProLinx Communication Gateway

Protocol Manual

IEC 60870-5-101 v3 Slave (Firmware version 3.xx)

Page 40 of 159

ProSoft Technology, Inc.

August 6, 2010

Parameter

Description

Range

C_RC_NA point count

The number of point values assigned in command

step-point database.

0 to 1000

C_BO_NA point count

The number of 32-bit values assigned in command

bitstring database

0 to 1000

C_SE_NA point count

The number of point values assigned in command

normalized-point database.

0 to 1000

C_SE_NB point count

The number of point values assigned in command

scaled-point database.

0 to 1000

C_SE_NC point count

The number of point values assigned in command

short-float point database.

0 to 50

2.2.4 Sequence Flag

In order to save bandwidth, you can configure the gateway to use the Sequence

Flag feature. If this feature is not selected, the gateway will send the Information

Object Address (IOA) and the data value for every Monitor information object in

a poll response to the Master. If this parameter is enabled, the gateway will turn

on the Sequence Flag bit in a Monitor response; send the Informaiton Object

Address of only the first object in the response, along with its data value; and

send only the data values for all the other information objects in the response.

The Master assumes that all other points use IOAs in a contiguous order (using

the first point as the starting reference address). Since the IOAs are omitted for

all but the first point, this feature allows each message packet to contain more

process data, which improves network throughput and optimizes bandwidth

utilization.