C_sc_na and c_dc_na – ProSoft Technology 5201-MNET-101S User Manual

Page 94

Advertising
background image

Reference

IEC-101 Slave ♦ ProLinx Communication Gateway

Protocol Manual

IEC 60870-5-101 v3 Slave (Firmware version 3.xx)

Page 94 of 159

ProSoft Technology, Inc.

August 6, 2010

C_SC_NA and C_DC_NA
The single-point command and dual-point command points use one bit with bit-

addressing. For example, if you configure the following points:

The following table describes how these points would be used.

Inf. Object Address

Module Database Address

100

Bit 0 of word 100

101

Bit 1 of word 100

102

Bit 2 of word 100

The protocol specification defines a qualifier value that is set by the Master to

determine the duration of the pulse (short, long or persistent). Configure the

Short Pulse Time and Long Pulse Time parameters, seen below, to set the

duration of the short and long pulses: