IEC-101 Slave ♦ ProLinx Communication Gateway

Reference

IEC 60870-5-101 v3 Slave (Firmware version 3.xx)

Protocol Manual

ProSoft Technology, Inc.

Page 117 of 159

August 6, 2010

Example 1 - Command Request Without Response only
For this example, the remote node is passing a timestamp event to be

transferred to the remote client connected to the ProLinx gateway.

The following block can be used for the first request.

Command Request Block

Word

Offset

Database

Address

Value

Description

0

3000

100

Block ID1 - Command Request Without Response

1

3001

0

Block ID2 - Command Request With Response. Move

a value of 0 or any other value out of the 200 to 203

range since no data is requested back from the

gateway

2 to 10

3002 to 3010 Event Data

Timestamp event

99

3099

100

Block ID1 - Command Request Without Response


Command Response Block

Word Offset Database

Address

Value

Description

0

3100

0

Block ID2 - Command Request With Response.

1

3101

100

Block ID1 - Command Request Without Response

2 to 98

3102 to 3198 Reserved

Reserved - no update

99

3199

0

Block ID2 - Command Request With Response.

In order to send another command request to pass another event, use the

following format:

Command Request Block

Word

Offset

Database

Address

Value

Description

0

3000

101

Block ID1 - Command Request Without Response

1

3001

0

Block ID2 - Command Request With Response. Move

a value of 0 or any other value out of the 200 to 203

range since no data is requested back from the

gateway

2 to 10

3002 to 3010 Event Data

Timestamp event

99

3099

101

Block ID1 - Command Request Without Response

Advertising