M_st_na_1, M_bo_na_1 104 – ProSoft Technology 5201-MNET-101S User Manual

Page 43

Advertising
background image

IEC-101 Slave ♦ ProLinx Communication Gateway

101S Protocol Configuration

IEC 60870-5-101 v3 Slave (Firmware version 3.xx)

Protocol Manual

ProSoft Technology, Inc.

Page 43 of 159

August 6, 2010

2.5 [M_ST_NA_1]

This section defines the monitored step database. This information is sourced

from the database and is transferred to the remote Master unit.
This section takes the following parameters:

P

OINT

#

DB

ADDRESS

G

ROUPS

(page 50)

IV

DB

B

IT

Each point consumes one, 8-bit byte. The

DB

A

DDRESS

value corresponds to the

byte offset address in the database.
The

DB

ADDRESS

should be located in a database area that is being constantly

moved from the gateway to the Master.
For additional information on how to set these parameters, see the Reference

chapter of this manual.

2.6 [M_BO_NA_1 104]

This section defines the Monitored 32-bit Bitstring Data Point database. This

information is sourced from the database and is transferred to the remote Master

unit.
This section takes the following parameters:

Point #

DB Address

Groups (page 50)

IV DB Bit

Each point is four 8-bit bytes (two 16-bit words) and the DB Address value

corresponds to the double word offset in the gateway memory database.
The DB address should be located in a database area that is being constantly

moved from the gateway to the Master.
For additional information on how to set these parameters, see the Reference

chapter of this manual.