Parameter offset – ProSoft Technology 5201-MNET-101S User Manual

Page 41

Advertising
background image

IEC-101 Slave ♦ ProLinx Communication Gateway

101S Protocol Configuration

IEC 60870-5-101 v3 Slave (Firmware version 3.xx)

Protocol Manual

ProSoft Technology, Inc.

Page 41 of 159

August 6, 2010

2.2.5 Parameter Offset

This parameter specifies the IOA (Information Object Address) offset to the

parameter data for the normalized parameter data. The value entered is added to

the Information Object address for the associated point to compute the

parameter IOA address.
The Master may send a "Parameter of Measured Normalized" or "Parameter of

Measured Scaled" command using the parameter IOA in order to change the

deadband values for specific points.

Note: The Low Limit and High Limit values are always calculated based on the deadband value as

described in the following table.

Point

Value

Threshold

Determined by the deadband set in the configuration file or altered by the write

command.

Low

Last reported event value - threshold.

High

Last reported event value + threshold.

For example, if the configuration sets two M_ME_NA points with IOA (Point #) of

600 and 601 and an M_ME_NA Parameter Offset value of 3000, it would result in

the parameter points shown in the table.