Command request block, Command response block – ProSoft Technology 5201-MNET-101S User Manual

Page 122

Advertising
background image

Reference

IEC-101 Slave ♦ ProLinx Communication Gateway

Protocol Manual

IEC 60870-5-101 v3 Slave (Firmware version 3.xx)

Page 122 of 159

ProSoft Technology, Inc.

August 6, 2010

Command Request Block

Word

Offset

Database

Address

Value

Description

0

3000

201

Block ID1 - Command Request Without Response (Set

Time)

1

3001

201

Block ID2 - Command Request With Response (Get

Time)

2 to 98

3002 to 3008 New Time

Sent to

ProLinx

New Time Sent to ProLinx

99

3099

201

Block ID1 - (Set Time)


Command Response Block

Word

Offset

Database

Address

Value

Description

0

3100

201

Block ID2 - Command Request With Response (Get

Time)

1

3101

201

Block ID1 - Command Request Without Response (Set

Time)

2 to 8

3102 to 3108 Event Buffers Current Time sent by ProLinx

99

3199

201

Block ID2 - Command Request With Response (Get

Time)

Advertising
This manual is related to the following products: