Data Link Configuration
The protocol specification document IEC 60870-5-2 specifies an unambiguous

address (number) must be used for each link. Each address may be unique

within a specific system, or may be unique within a group of links sharing a

common channel. The protocol specification defines that the Data Link Address

may have 0, 1 or 2 octets. The first option should be used only during Balanced

Mode.

Configure the Data Link Address Length parameter to set the number of octets to

be used for the Data Link Address value. It is essential that the Master unit also

uses the same number of octets configured in the 101 Slave. Values shown here

are for example only. Your application may require different settings.

Data Link Address Length: 1

You must also configure the actual Data Link Address value using the following

parameter:

Data link address: 1

This value identifies the gateway’s address in the network.