101S Protocol Configuration

IEC-101 Slave ♦ ProLinx Communication Gateway

Protocol Manual

IEC 60870-5-101 v3 Slave (Firmware version 3.xx)

Page 28 of 159

ProSoft Technology, Inc.

August 6, 2010

Example I - Freeze Start Type
If the gateway should send the counter points on the hourly turn around time and

also 45 minutes later, the Mode A parameters should be configured as follows:

So the gateway would send events as follows (Hours:Minutes:Seconds):

17:00:00

17:45:00

18:00:00

18:45:00

19:00:00

19:45:00

The following illustration shows a typical communication example when the Mode

A is selected during unbalanced mode operation: