IEC-101 Slave ♦ ProLinx Communication Gateway

Reference

IEC 60870-5-101 v3 Slave (Firmware version 3.xx)

Protocol Manual

ProSoft Technology, Inc.

Page 97 of 159

August 6, 2010

C_SE_NA and C_SE_NB
The Control Normalized Value Set Point Command information object and the

Control Scaled Value Set Point Command information object use one word with

word addressing. For example, if you configured the following points:

The following table describes how these points would be used.

Inf. Object Address

Module Database Address

1100

Word 2000 (Word address 2000)

400

Word 10 (Word address 10. Must match the

configuration of point 400 in M_ME_NA.)

1101

Word 2001 (Word address 2001)

401

Word 12 (Word address 12. Must match the

configuration of point 401 in M_ME_NA.)

1102

Word 2002 (Word address 2002)

402

Word 18 (Word address 18. Must match the

configuration of point 402 in M_ME_NA.)

The Control Normalized Measured information objects use a data representation

defined by the protocol specification to represent fractional decimal values. The

following table describes the value for each bit as a reciprocal power of two (2),

that is two (2) raised to the power of a negative exponent (-1 through -15). Bit 15

is the Sign Bit.

Bit

15

14

13

12

11

10

9

8

7 6 5 4 3 2 1 0

Value

Hex(h)

Decimal

Sign 4000h

2

-1

2000h

2

-2

1000h

2

-3

800

h

2

-4

400

h

2

-5

200

h

2

-6

100

h

2

-7

80

h

2

-8

40

h

2

-9

20

h

2

-10

10

h

2

-11

8h

2

-12

4h

2

-13

2h

2

-14

1h

2

-15

4000h

0.5

0 1

0

0

0 0 0 0 0 0 0 0 0 0 0 0

2000h

0.25

0 0

1

0

0 0 0 0 0 0 0 0 0 0 0 0

1000h

0.125

0 0

0

1

0 0 0 0 0 0 0 0 0 0 0 0

6000h

0.75

0 1

1

0

0 0 0 0 0 0 0 0 0 0 0 0

3210h

0.395751953125

0 0

1

1

0 0 1 0 0 0 0 1 0 0 0 0