Gateway Communication Ports

IEC-101 Slave ♦ ProLinx Communication Gateway

Protocol Manual

IEC 60870-5-101 v3 Slave (Firmware version 3.xx)

Page 54 of 159

ProSoft Technology, Inc.

August 6, 2010

3.3.3 RS-232: Null Modem Connection (No Hardware Handshaking)

This type of connection can be used to connect the gateway to a computer or

field device communication port.

Note: For most null modem connections where hardware handshaking is not required, the Use

CTS Line parameter should be set to N

and no jumper will be required between Pins 7 (RTS) and 8

(CTS) on the connector. If the port is configured with the Use CTS Line set to Y, then a jumper is

required between the RTS and the CTS lines on the port connection.