2.1.20 Event Priority

Event Priority permits the user to set reporting priorities for data change events

generated for each data type. The configuration file contains the following

parameters to support this feature:

The Set Priority Queues parameter must be enabled for this feature to be used.

Each of the Monitored Point ASDUs must be assigned a unique priority index

from 0 to 7. When events of the ASDU with a lower priority number are present,

they will always be reported before events from any other ASDUs with higher

priority numbers.

2.1.21 Cyclic Set IV Time - PLX 101S

1 to 65535 seconds, or 0 to disable Invalid Bit Monitoring
The parameter should be set to a value significantly greater than the value of the

IV Check Delay Time parameter, multiplied by the value of the IV Fail Count

parameter. Example:

If, IV Check Delay =

3;

And, IV Fail Count =

5;

Then set Cyclic Set IV Time significantly greater than 15; preferably some

multiple of this value, like

30, 45, 60,

or more.

The Cyclic Set IV Time parameter is one of three parameters needed to establish

a fail-safe data validation system for this protocol implementation. This

parameter is used with the IV Check Delay Time and the IV Fail Count

parameters to create a way to alert the remote IEC-101 Master to situations

where data being sent by the gateway might be invalid.