2.1.8 Inform. Object Address Len

1, 2, or 3
This parameter specifies the number of octets used to define the address of an

information object (point address).

2.1.9 Cyclic Data Transmission

0 to 4,294,967,296 (2 raised to the power of 32) milliseconds
This parameter defines the number of milliseconds between cyclic updates. The

range of values allow for update times between 1 millisecond and 49.7 days. Set

this parameter to 0 to disable cyclic data reporting.

2.1.10 Select/Operate Timeout

0 to 4,294,967,296 (2 raised to the power of 32) milliseconds
This parameter sets the number of milliseconds to wait for a valid Execute

command after receiving a Select command. The range of values allows for

update times between 1 millisecond and 49.7 days. Set this parameter to

0 to

disable this feature.

2.1.11 Use ACTTERM with Set Point

Y - Y

ES

or

N - N

O

This parameter determines if an ACTTERM will be sent. If the parameter is set to

Y

ES

, then set point commands will issue an ACTTERM when the command is

complete. If the parameter is set to

N

O

, ACTCON is the last response to a set

point command.

2.1.12 Use ACTTERM with Step

Y - Y

ES

or

N - N

O

This parameter determines if an ACTTERM will be sent. If the parameter is set to

Y

ES

, then step commands will issue an ACTTERM when the command is

complete. If the parameter is set to

N

O

, ACTCON is the last response to a step

command.

2.1.13 Single char ACK F0, 1 or 3

Y

-

Y

ES

or

N

-

N

O

If set to Yes, a single character ACK (0xE5) will be sent instead of a fixed length

ACK (secondary function code 0) in response to a primary link function code 0, 1

or 3 if there is no access demand for class 1 data (ACD=1). If set to No, the fixed

length ACK will be sent.