2.18 Group Codes

Note that the highest bit assigns the point to the cyclic data group. This data will

be cyclically reported to the Master at the frequency set in the configuration value

"Cyclic Data Transmission" Parameter.

Group Code

Description

0x00000001

Interrogated by general interrogation (station or global)

0x00000002

Interrogated by group 1 interrogation

0x00000004

Interrogated by group 2 interrogation

0x00000008

Interrogated by group 3 interrogation

0x00000010

Interrogated by group 4 interrogation

0x00000020

Interrogated by group 5 interrogation

0x00000040

Interrogated by group 6 interrogation

0x00000080

Interrogated by group 7 interrogation

0x00000100

Interrogated by group 8 interrogation

0x00000200

Interrogated by group 9 interrogation

0x00000400

Interrogated by group 10 interrogation

0x00000800

Interrogated by group 11 interrogation

0x00001000

Interrogated by group 12 interrogation

0x00002000

Interrogated by group 13 interrogation

0x00004000

Interrogated by group 14 interrogation

0x00008000

Interrogated by group 15 interrogation

0x00010000

Interrogated by group 16 interrogation

0x00020000

Interrogated by general counter request

0x00040000

Interrogated by group 1 counter request

0x00080000

Interrogated by group 2 counter request

0x00100000

Interrogated by group 3 counter request

0x00200000

Interrogated by group 4 counter request

0x40000000

Disable event scanning of this point

0x80000000

Periodic/cyclic data returned from unit

If the highest bit (bit 31) is set, data will be produced by the driver for the

specified point at the rate set for periodic data generation. Bit 30 (0x40000000)

enables scanning of this point for event generation. If the bit is clear and the data

type is set for scanning, events will be generated for the point. If the bit is set,

events will not be generated for the point. This feature can be used to select

which points will generate events for the controlling station and can get rid of

event data that is not important to the application

Advertising
This manual is related to the following products: