M_me_nc and m_it_na – ProSoft Technology 5201-MNET-101S User Manual

Page 87

Advertising
background image

IEC-101 Slave ♦ ProLinx Communication Gateway

Reference

IEC 60870-5-101 v3 Slave (Firmware version 3.xx)

Protocol Manual

ProSoft Technology, Inc.

Page 87 of 159

August 6, 2010

Examples:
A value of 4000hex (only Bit 14 set, all others clear) is interpreted as 0.5 decimal
A value of 2000hex (only Bit 13 set, all others clear) is interpreted as 0.25

decimal
A value of 1000hex (only Bit 12 set, all others clear) is interpreted as 0.125

decimal
... and so on until...
A value of 0001hex (Only Bit 0 set, all others clear) is interpreted as

0.000030517578125
Therefore, the actual data values transmitted may be any combination of the

decimal values for any given bit pattern.

M_ME_NC and M_IT_NA
The Monitor Short Floating-Point Measured Value and Monitored Integrated

Totals information objects occupy two words with double-word addressing.
For example, if you configured the following points:

The following table describes how these points would be stored in the gateway.

Inf. Object Address

Module Database Address

500

Words 40 and 41 (Double-word address 20)

501

Words 64 and 65 (Double-word address 32)

502

Word 104 and 105 (Double-word address 52)