IEC-101 Slave ♦ ProLinx Communication Gateway

Reference

IEC 60870-5-101 v3 Slave (Firmware version 3.xx)

Protocol Manual

ProSoft Technology, Inc.

Page 127 of 159

August 6, 2010

Get Event Buffer Counts Command Block
This functionality allows a remote node to retrieve the event buffer space of each

data type. The following tables describe the structure of the Get Event Buffer

Sizes command block:

Request Block

Start Word

End Word

Description

0

0

Block ID1 (Command Request Without Response)

1

1

202 or 203 = Get Event Buffer Count (Block ID2)

2

2

Reserved

3

98

Reserved

99

99

Block ID1

Response Block

Start Word

End Word

Description

0

0

202 or 203 = Get Event Buffer Count (Block ID2)

1

1

Block ID1 (Command Request Without Response)

2

2

Single point event buffer space

3

3

Double point event buffer space

4

4

Step point event buffer space

5

5

Normalized event buffer space

6

6

Scaled event buffer space

7

7

Short-float event buffer space

8

8

Integrated totals event buffer space

9

98

Reserved

99

99

202 or 203 = Get Event Buffer Count (Block ID2)