Disable time sync events, Data link address value, Data link address length – ProSoft Technology 5201-MNET-101S User Manual

Page 25: Common address of asdu val, Common address of asdu len

Advertising
background image

IEC-101 Slave ♦ ProLinx Communication Gateway

101S Protocol Configuration

IEC 60870-5-101 v3 Slave (Firmware version 3.xx)

Protocol Manual

ProSoft Technology, Inc.

Page 25 of 159

August 6, 2010

2.1.3 Disable Time Sync Events

Y

ES

or

N

O

This feature can be used when the Master receives the event timestamp with

only minutes and milliseconds information for each event message (CP24 time

type). If the parameter is set to

N, the spontaneous time sync events will be

generated to indicate the change of hour. If this parameter is set to

Y, then the

spontaneous time sync event messages are not generated to indicate the

change of hour.

2.1.4 Data Link Address Value

0 to

65535

This parameter defines the Data Link Address for the emulated device on the

gateway. This address identifies the gateway on the network along with the

common address of ASDU.

2.1.5 Data link address length

0, 1, or 2
This parameter specifies the number of octets used for the data link address.

This parameter must be set the same for all devices on the network. A value of 0

is only valid when the balanced mode is used. If unbalanced mode is used, a

value of 1 or 2 must be used.

2.1.6 Common Address of ASDU Val

0

to

65535

This parameter specifies the common address of the ASDU (section address) for

access to data in the gateway. There is only one value entered for access to all

data in the gateway.
Refer to ASDU Configuration for more information on Application Service Data

Unit configuration.

2.1.7 Common Address of ASDU Len

1 or 2
This parameter specifies the number of octets used for the common address of

ASDU. This parameter must be set the same for all devices on the network.