When in trouble, 1)outline, 2) applicable range – Panasonic MINAS A4P Series User Manual

Page 170

Advertising
background image

170

When in Trouble

100

115

0.1

1

10

100

150

200

250

300

350

400

450

500

torque [100%]

time [sec]

Overload protection time characteristics (Motor type M*MA)

MAMA 100W
MQMA 100W

to

400W

MAMA 200W

to

750W

MSMA 1kW

to

5kW

MDMA 1kW

to

5kW

MHMA 1kW

to

5kW

MFMA 400W

to

4.5kW

MGMA 900W

to

4.5kW

100

0.1

1

10

100

150

200

250

300

350

400

450

500

115

time [sec]

Overload protection time characteristics (Motor type M*MD)

MSMD 50W
MSMD 100W (100V)
MSMD 100W (200V)
MSMD 200W
MSMD 400W
MSMD 750W

torque [100%]

Control mode

Others

Conditions under which the software limit works

• Either at position control mode or full-closed control mode
SV.Pr02 = 0 : Position control
SV.Pr02 = 6 : Full-closed control

(1) operating Normal auto tuning
(2) After the last clearance of the position command input range (0 clearance), the movable range

of the motor is within 2147483647 for both CCW and CW direction.

(3) at Servo-ON
(2) when SV.Pr26 (Software limit setup) is other than 0.

Once the motor gets out of the (2) condition, the software limit protection will be invalidated

until the later mentioned "5) Condition under which the position command input range is
cleared" is satisfied. The position command input range will be 0-cleared when the motor gets
out of the conditions of (3) and (4).

• Time characteristics of Err16 (Overload protection)

• Software Limit Function

1)Outline

You can make an alarm stop of the motor with software limit protection (Error code No.34) when the
motor travels exceeding the movable range which is set up with SV.Pr26 (Software limit set up) against
the position command input range.
You can prevent the work from colliding to the machine end caused by motor oscillation.

2) Applicable range

This function works under the following conditions.