Preparation, Tips on wiring – Panasonic MINAS A4P Series User Manual

Page 41

Advertising
background image

41

[Preparation]

Preparation

Wiring to the Connector, CN X5 (Connection to Host Controller)

• Tips on wiring

Controller

3m

or shorter

30cm or longer

COM+

GND

1

CN X5

COM–

FG

V

DC

Power

supply

Motor

2

Peripheral apparatus such as host controller should be located
within 3m.

Separate the main circuit at least 30cm away.
Don't pass them in the same duct, nor bind them together.

Power supply for control signals (V

CC

) between COM+ and COM– (V

DC

)

should be prepared by customer.

Use shield twisted pair for the wiring of encoder signal output.

Don't apply more than 24V to the control signal output terminals, nor run
50mA or more to them.

When the relay is directly driven by the control output signals, install a
diode in parallel with a relay, and in the direction as the Fig. shows. The
driver might be damaged without a diode installment, or by reverse
direction.

Frame ground (FG) is connected to the earth terminal inside of the
driver.

• For detailed information, refer to P.42 to 47.

• Specifications of the Connector, CN X5

<Note>
For details, refer to P.185, "Options" of Supplement.

<Remarks>
• Tightening torque of the screws for connector (CN X5) for the connection to the host to be 0.3 to 0.35N

m.

Larger tightening torque than these may damage the connector at the driver side.

Connector at driver side

52986-3679

Part name

Connecter (soldering type)

Connector cover

Connecter (soldering type)
Connector cover

Part No.

54306-3611 or

54306-3619 (lead-free)

54331-0361

10136-3000VE

10336-52A0-008

Connecter to be prepared by customer

Manufacturer

Molex Inc.

Sumitomo 3M

or