Parameter Setup

Standard default : < >

Servo

PrNo.

Setup

range

Unit

Title

Function/Content

69

0 to 9

<0>

Sequence at

Servo-OFF

You can set up,
1) the running condition during deceleration and after stalling
2) the clear treatment of deviation counter is set up.
After the servo-ON signal input is turned off (SRV-ON : CN X5, Pin-23
shifting from ON to OFF).
The relation between the setup value of SV.Pr69 and the action/deviation
counter clearance is same as that of SV.Pr67 (Error response at main
power-off).
Refer to P.135, "Timing Chart"-Servo-ON/OFF action while the motor is at
stall" of Operation Setting as well.

6A

0 to 100

<0>

2ms

Mechanical brake

delay at motor

standstill

You can set up the time from when the brake release signal (BRK-OFF :
CN X5, Pin-10 and 11) turns off to when the motor is de-energized
(Servo-free), when the motor turns to Servo-OFF while the motor is at
stall.

Refer to P.135, "Timing Chart"-Servo-ON/OFF Action While the Motor Is
at Stall" of Operation Setting as well.

• Set up to prevent a micro-travel/

drop of the motor (work) due to the
action delay time (tb) of the brake

• After setting up SV.Pr6a

>

=

tb ,

then compose the sequence so as

the driver turns to Servo-OFF after
the brake is actually activated.

ON

SRV-ON

BRK-OFF

actual brake

motor
energization

release

OFF

hold

release

energized

hold

non-

energized

Pr6A

tb

6B

0 to 100

<0>

2ms

Mechanical brake

delay at motor in

motion

You can set up time from when detecting the off of Servo-ON input signal
(SRV-ON : CN X5, Pin-29) is to when external brake release signal
(BRK-OFF : CN X5, Pin-10 and 11) turns off, while the motor turns to
servo off during the motor in motion.

Refer to P.135, "Timing Chart"-Servo-ON/OFF action while the motor is in
motion" of Operation Setting as well.

• Set up to prevent the brake

deterioration due to the motor
running.

• At Servo-OFF during the motor is

running, tb of the right fig. will be
a shorter one of either SV.Pr6B
setup time, or time lapse till the
motor speed falls below 30r/min.

tb

ON

SRV-ON

BRK-OFF

motor
energization

release

OFF

hold

actual
brake

energized

non-

energized

30 r/min

<Notes>
• For servo parameters which No. have a suffix of "*", changed contents will be validated when you turn on

the control power.