[Preparation]

Preparation

• Select a single and 3-phase common specifications according to the power source.
• Manufacturer of circuit breaker and magnetic contactor : Matsushita Electric Works.

To comply to EC Directives, install a circuit breaker between the power and the noise filter without fail, and
the circuit breaker should conform to IEC Standards and UL recognized (Listed and marked).
5000Arms, 240V is the maximum capacity to be delivered to the circuit of 750W or larger model when the
maximum current value of the circuit breaker is limited to 20A.

• For details of noise filters, refer to P.177, 178, "Noise Filter" and P.179, "Driver and List of Applicable

Peripheral Equipments (EC Directives)" of Supplement.

<Remarks>
• Select and use the circuit breaker and noise filter with matching capacity to those of the power source,

considering the load conditions as well.

• Terminal block and protective earth terminal

Use a copper conductor cable with temperature rating of 60˚C or higher.
Protective earth terminal is M4 for A to D-frame, and M5 for E and F-frame.
Larger tightening torque of the screw than the max. value (M4 : 1.2 N

m, M5 : 2.0 N

m) may damage the

terminal block.

• Earth cable diameter should be 2.0mm

2

(AWG14) or larger for 50W to 2.0kW model, and 3.5mm

2

(AWG12)

or larger for 2.5kW to 4.0kW, and 5.3mm

2

(AWG10) or larger for 4.5kW to 5kW model.

• Use the attached exclusive connectors for A to D-frame, and maintain the peeled off length of 8 to 9mm.
• Tightening torque of the screws for connector (CN X5) for the connection to the host to be 0.3 to 0.35 N

m.

Larger tightening torque than these may damage the connector at the driver side.

Connection

Driver

Applicable

motor

Voltage

Rated

output

Required

Power

(at the rated

load)

Noise filter

for signal

Noise

filter

Surge

absorber

Magnetic

contactor

Cable

diameter

(main circuit)

Cable

diameter

(control circuit)

Circuit

breaker

(rated

current)

MFDD

MGMA

MDMA

MHMA

MSMA

MGMA

MDMA

MHMA

MSMA

MFMA

MGMA

MDMA

MHMA

MSMA

3- phase,

200V

2.0kW

3.0kW

4.0kW

4.5kW

5.0kW

approx.

3.8kVA

approx.

4.5kVA

approx.

6kVA

approx.

6.8kVA

approx.

7.5kVA

approx.

7.5kVA

50A

DV0P3410 DV0P1450 DV0P1460

BMF6352N

(3P+2a2b)

BMF6652N

(3P+2a2b)

3.5mm

2

AWG12

5.3mm

2

AWG10

0.75mm

2

AWG18

Terminal

block

M5

11.0 or

smaller

ш5.3