Setting, Parameters for protective function – Panasonic MINAS A4P Series User Manual

Page 71

Advertising
background image

71

[Setting]

Setting

Standard default : < >

Servo

PrNo.

Setup

range

Unit

Title

Function/Content

6C

*

0 to 3

for

A, B-frame

<3>

for

C to F-frame

<0>

External

regenerative

resistor set up

With this parameter, you can select either to use the built-in regenerative
resistor of the driver, or to separate this built-in regenerative resistor and
externally install the regenerative resistor (between RB1 and RB2 of
Connector CN X2 in case of A to D-frame, between P and B2 of terminal
block in case of E, F-frame).

<Remarks>
Install an external protection such as thermal fuse when you use the
external regenerative resistor.
Otherwise, the regenerative resistor might be heated up abnormally and
result in burnout, regardless of validation or invalidation of regenerative
over-road protection.
<Caution>
When you use the built-in regenerative resistor, never to set up other
value than 0. Don't touch the external regenerative resistor.
External regenerative resistor gets very hot, and might cause burning.

Setup value

<0>

(C, D, E and

F-frame)

1

2

<3>

(A, B-frame)

Built-in resistor

External resistor

External resistor

No resistor

Regenerative processing circuit will be
activated and regenerative resistor overload
protection will be triggered according to the
built-in resistor (approx. 1% duty).
The driver trips due to regenerative overload
protection (Err18), when regenerative
processing circuit is activated and its active
ratio exceeds 10%,
Regenerative processing circuit is activated,
but no regenerative over-load protection is
triggered.
Both regenerative processing circuit and
regenerative protection are not activated, and
built-in capacitor handles all regenerative
power.

Regenerative resistor

to be used

Regenerative processing and

regenerative resistor overload

6D

*

35 to 1000

<35>

2ms

Main power-off

detection time

You can set up the time to detect the shutoff while the main power is kept

shut off continuously.

The main power off detection is invalid when you set up this to 1000.

6E

0 to 500

<0>

%

Emergency stop

torque set up

You can set up the torque limit in case of emergency stop as below.
• During deceleration with the setup of 8 or 9 of SV.Pr67 (Error response

at main power-off)

• During deceleration with the setup of 8 or 9 of SV.Pr69 (Sequence at

Servo-OFF)

Normal torque limit is used by setting this to 0.
<Caution>
The stop is not due to the emergency stop input (EMG-STP: CN X5 Pin 2).

Standard default : < >

Servo

PrNo.

Setup

range

Unit

Title

Function/Content

70

0 to 32767

<25000>

256 x

pulse

Position deviation

error level

• You can set up the excess range of position deviation.

• Set up with the encoder pulse counts at the position control and with the

external scale pulse counts at the full-closed control.

• Err24 (Position deviation excess protection) becomes invalid when you

set up this to 0.

72

0 to 500

<0>

%

Overload level

• You can set up the over-load level. The overload level becomes 115 [%]

by setting up this to 0.

• Use this with 0 setup in normal operation. Set up other value only when

you need to lower the over-load level.

• The setup value of this parameter is limited by 115[%] of the motor rating.

Parameters for Protective function