Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual

Page 100

Advertising
background image

5–22

Programming

[Speed Control]

This parameter selects the type of speed modulation
active in the drive.

This parameter cannot be changed while the drive is
running.

Important: If encoder feedback closed loop speed
regulation is required, “Encoder Fdbk” must be
selected.

Parameter Number

77

Parameter Type

Read and Write

Factory Default

“Slip Comp” (“No Control” frn < 4.01)

Units

Display Drive

“No Control” 0

Frequency regulation

“Slip Comp” 1

Slip compensation

“Speed Droop” 2

Negative slip compensation

“PLL” 3

Phase lock loop (requires frn < 4.01)

“Encoder Fdbk” 4

Encoder feedback–closed loop

“Droop + Reg” 5

Enc. fdbk.–closed loop w/ active droop

“P Jump” 6

Traverse function

“Process PI” 7

Closed loop PI control

[Slip @ F.L.A.]

This value sets the amount of automatic increase or
decrease to the drive output to compensate for
motor slip. When [Speed Control] is set to “Slip
Comp”, a percentage of this value proportional to
output current is added to the drive output
frequency. When [Speed Control] is set to “Droop”, a
percentage of this value proportional to output
current is subtracted from the drive output
frequency.

Parameter Number

42

Parameter Type

Read and Write

Display Units / Drive Units

0.1 Hertz / Hertz x 10

Factory Default

1.0 Hz (0.0 Hz frn < 4.01)

Minimum Value

0.0 Hz

Maximum Value

10.0 Hz (5.0 frn < 4.01)

[Slip Comp Gain]– Firmware 4.01 & later

This parameter is the gain for the slip compensation
and adjusts the recovery rate after a load change.

Parameter Number

195

Parameter Type

Read and Write

Display Units / Drive Units

None

Factory Default

1

Minimum Value

1

Maximum Value

40

[Run On Power Up]

This parameter enables the function that allows the
drive to automatically restart on Power Up. This
parameter requires that a two wire control scheme
be installed at TB3 and that a valid start contact be
present. Refer to Input Mode Selection figure in
Chapter 2.

Parameter Number

14

Parameter Type

Read and Write

Factory Default

“Disabled”

Units

Display Drive

“Disabled” 0

“Enabled” 1

ATTENTION: This parameter may only be used as outlined in
NFPA79, paragraph 6-14 (exceptions 1-3) for specialized
applications. Equipment damage and/or personal injury may
result if this parameter is used in an inappropriate application.

!

[Reset/Run Tries]

This value sets the maximum number of times the
drive attempts to reset a fault and restart before the
drive issues a “Max Retries Fault”. See Chapter 6 for
a list of resettable faults.

Parameter Number

85

Parameter Type

Read and Write

Display Units / Drive Units

1 Try / Tries

Factory Default

0

Minimum Value

0

Maximum Value

9

Feature Select