Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual
Page 100
5–22
Programming
[Speed Control]
This parameter selects the type of speed modulation
active in the drive.
This parameter cannot be changed while the drive is
running.
Important: If encoder feedback closed loop speed
regulation is required, “Encoder Fdbk” must be
selected.
Parameter Number
77
Parameter Type
Read and Write
Factory Default
“Slip Comp” (“No Control” frn < 4.01)
Units
Display Drive
“No Control” 0
Frequency regulation
“Slip Comp” 1
Slip compensation
“Speed Droop” 2
Negative slip compensation
“PLL” 3
Phase lock loop (requires frn < 4.01)
“Encoder Fdbk” 4
Encoder feedback–closed loop
“Droop + Reg” 5
Enc. fdbk.–closed loop w/ active droop
“P Jump” 6
Traverse function
“Process PI” 7
Closed loop PI control
[Slip @ F.L.A.]
This value sets the amount of automatic increase or
decrease to the drive output to compensate for
motor slip. When [Speed Control] is set to “Slip
Comp”, a percentage of this value proportional to
output current is added to the drive output
frequency. When [Speed Control] is set to “Droop”, a
percentage of this value proportional to output
current is subtracted from the drive output
frequency.
Parameter Number
42
Parameter Type
Read and Write
Display Units / Drive Units
0.1 Hertz / Hertz x 10
Factory Default
1.0 Hz (0.0 Hz frn < 4.01)
Minimum Value
0.0 Hz
Maximum Value
10.0 Hz (5.0 frn < 4.01)
[Slip Comp Gain]– Firmware 4.01 & later
This parameter is the gain for the slip compensation
and adjusts the recovery rate after a load change.
Parameter Number
195
Parameter Type
Read and Write
Display Units / Drive Units
None
Factory Default
1
Minimum Value
1
Maximum Value
40
[Run On Power Up]
This parameter enables the function that allows the
drive to automatically restart on Power Up. This
parameter requires that a two wire control scheme
be installed at TB3 and that a valid start contact be
present. Refer to Input Mode Selection figure in
Chapter 2.
Parameter Number
14
Parameter Type
Read and Write
Factory Default
“Disabled”
Units
Display Drive
“Disabled” 0
“Enabled” 1
ATTENTION: This parameter may only be used as outlined in
NFPA79, paragraph 6-14 (exceptions 1-3) for specialized
applications. Equipment damage and/or personal injury may
result if this parameter is used in an inappropriate application.
!
[Reset/Run Tries]
This value sets the maximum number of times the
drive attempts to reset a fault and restart before the
drive issues a “Max Retries Fault”. See Chapter 6 for
a list of resettable faults.
Parameter Number
85
Parameter Type
Read and Write
Display Units / Drive Units
1 Try / Tries
Factory Default
0
Minimum Value
0
Maximum Value
9
Feature Select