Pi preload] – firmware 4.01 & later – Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual

Page 128

Advertising
background image

5–50

Programming

[PI Preload] – Firmware 4.01 & later

Sets the value used to preload the PI intergrator
when “Set Output” or “Preload Int” bits equal “1” in
[PI Config].

Parameter Number

225

Parameter Type

Read/Write

Display Units / Drive Units

0.01 Hertz /

±

32767 = Maximum Freq

Factory Default

0.00 Hz

Minimum Value

– 8.33% of [Maximum Freq]

Maximum Value

+ 8.33% of [Maximum Freq]

PI Reference

PI Reference

Select

pi reference

PI Config.sqrt_fdbk

PI Config.inv_error

PI Config.reset_int

PI Feedback

Freq Command

PI Error

Master Frequency Reference

Process KI

s

Process KP

Integral Term = 0

PI + Clamp

PI – Clamp

PI Output

Speed

Adder

Output Frequency

Speed

Command

Speed

Ramp

pi feedback

PI Feedback

Select

Compute

Speed

Accel

Control

+

–1

+

+

PI Config.zero_clamp

speed ramp>0

+

+

PI Output

+32767

Parameter 65

–32767

–32767

+32767

0

0

Process PI

Advertising