Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual

Page 37

Advertising
background image

2–27

Installation/Wiring

Example 2
Input Mode 7 – Application is to follow a local HIM unless a preset
speed is selected. The drive is programmed as follows:

[Freq Select 1] = Adapter 1

[Freq Select 2] = Preset Freq 1

[Preset Freq 1] = 10 Hz.

[Preset Freq 2] = 20 Hz.

[Preset Freq 3] = 30 Hz.

Contact operation for the speed select switch is described in the table
below. Since Input Mode 7 does not offer a Speed Select 3 input,
[Preset Freq 4-7] are not available.

26

Speed Select 2

Speed Select 1

Local

See Table

1 2

3

27

28

Switch

Speed Select Input

Parameter Used

Programmed

Switch
Position

1 (#28)

2 (#27)

Parameter Used
for Speed Ref.

Programmed
Setting

Local

Open

Open

[Freq Select 1]

Adapter 1

1

Closed

Open

[Freq Select 2]

Preset Freq 1

2

Open

Closed

[Preset Freq 2]

20 Hz.

3

Closed

Closed

[Preset Freq 3]

30 Hz.