Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual

Page 149

Advertising
background image

A–9

Specifications and Supplemental Information

Standard Rating for Enclosed Drive in
40

°

C Ambient & Open Drive in 50

°

C Ambient.

Derating Factor for Enclosed Drive in
Ambient between 41

°

C & 50

°

C.

Figure AA
1336S-C300 through C600
Enclosed Drive in 41

°

- 50

°

C Ambient

Carrier Frequency in kHz

2

3

4

50%

80%

90%

60%

40%

70%

100%

% of Drive

Rated Amps

Assumes two (2) 725 CFM cooling fans for
IP 20 (NEMA Type 1) enclosure

C300/

C350
C400

C450

C500

C600

6kHZ Data Not Available at Time of Printing

Figure Z
1336S-C300 through C600
Enclosed Drive in 40

°

C Ambient

Carrier Frequency in kHz

2

4

6

50%

80%

90%

60%

40%

70%

100%

% of Drive

Rated Amps

Assumes two (2) 725 CFM cooling fans for
IP 20 (NEMA Type 1) enclosure

C350

C300

C400
C450
C500
C600

Figure Y
1336S-CX300

Carrier Frequency in kHz

2

4

6

50%

80%

90%

60%

40%

70%

100%

% of Drive

Rated Amps

Figure X
1336S-C250

Carrier Frequency in kHz

2

4

6

50%

80%

90%

60%

40%

70%

100%

% of Drive

Rated Amps

ALTITUDE AND HIGH INPUT VOLTAGE

% of Drive

Rated Amps

Altitude

m

(ft)

100%

80%

90%

0

4,000

(13,200)

3,000

(9,900)

2,000

(6,600)

1,000

(3,300)

Figure BB
Altitude – All Drive Ratings

% of Drive

Rated Amps

Input Voltage

100%

80%

90%

240, 480 or 600V Nominal

+6%

+4%

+2%

+10%

+8%

Figure CC
High Input Voltage – Required Only for the following drives:

1336S-x025 – 18.5 kW (25 HP) at 8 kHz

1336S-x030 – 22 kW (30 HP) at 6 or 8 kHz
1336S-x060 – 45 kW (60 HP) at 6 kHz