User supplied enclosures, A–4 specifications and supplemental information – Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual

Page 144

Advertising
background image

A–4

Specifications and Supplemental Information

1336 plus drives installed in user supplied enclosures may be mounted
within an enclosure or may be mounted to allow the heat sink to
extend outside the enclosure. Use the information below in
combination with the enclosure manufacturer’s guidelines for sizing.

Cat No.

Base Derate
Amps

1

Derate
Curve

2, 3

Heat Dissipation
Drive Watts

2, 3, 4

Heat Sink
Watts

2

Total
Watts

2

200-240V DRIVES

AQF05
AQF07
AQF10
AQF15
AQF20
AQF30
AQF50

2.3
3.0
4.5
6.0
8.0
12
18

Figure A
Figure A
Figure A
Figure A
Figure A
Figure A
Figure A

13
15
17
21
25
33
42

15
21
32
42
56
72
116

28
36
49
63
81
105
158

A007
A010
A015
A020
A025
A030
A040
A050
A060
A075
A100
A125

27
34
48
65
77
80
120
150
180
240
291
325

None
Figure B
Figure D
None
None
None
Figure G
Figure H
Figure J
Figure L
Figure M
Figure N

156
200
205
210
215
220
361
426
522
606
755
902

486
721
819
933
1110
1110
1708
1944
2664
2769
3700
4100

642
921
1024
1143
1325
1330
2069
2370
3186
3375
4455
5002

380-480V DRIVES

BRF05
BRF07
BRF10
BRF15
BRF20
BRF30
BRF50
BRF75
BRF100

1.2
1.7
2.3
3.0
4.0
6.0
9.0
17.5
25.0

Figure A
Figure A
Figure A
Figure A
Figure A
Figure A
Figure A
Figure A
Figure A

12
13
15
16
19
23
29
70
89

9
15
20
27
36
54
84
230
331

21
28
35
43
55
77
113
300
420

B007
B010
B015
B020
B025
B030
BX040
B040
B050
BX060
B060
B075
B100
B125
BX150
B150
B200
B250
BP250
BX250
B300
BP300
B350
BP350
B400
BP400
B450
BP450
B500

5

B600

5

14
21
27
34
42
48
59
65
77
77
96
120
150
180
180
240
292
325
322
360
425
357
475
421
525
471
590
527
670
670

None
None
None
Figure B
Figure C
Figure D
Figure E
Figure E
Figure F
Figure F
None
Figure G
Figure H
Figure J
Figure J
Figure L
Figure M
Figure N
Figure O
None
None
Figure P
None
Figure Q
None
Figure R
None
Figure S
Figure T
Figure T

91
103
117
140
141
141
175
175
193
193
361
361
426
522
606
606
755
902
491
902
1005
619
1055
733
1295
793
1335
931
1395
1485

270
394
486
628
720
820
933
933
1110
1110
1708
1708
1944
2664
2769
2769
3700
4100
4658
4100
4805
5342
5455
6039
6175
6329
6875
7000
7525
8767

361
497
603
768
861
961
1108
1108
1303
1303
2069
2069
2370
3186
3375
3375
4455
5002
5149
5002
5810
5961
6510
6772
7470
7122
8210
7931
8920
10252

500-600V DRIVES

CW10
CW20
CW30
CW50

2.4
4.8
7.2
9.6

Figure U
Figure U
Figure U
Figure U

25
29
32
35

29
57
87
117

54
86
119
152

C007
C010
C015
C020
C025
C030
C040
C050
C060
C075
C100
C125
C150
C200
C250
CX300
C300

5

C350

5

C400

5

C450

5

C500

5

C600

5

10
12
19
24
30
35
45
57
62
85
109
138
158
252
284
300
300
350
400
450
500
600

None
None
None
None
None
None
None
None

6

Figure G
Figure I
Figure K
Figure V
Figure W
Figure X
Figure Y
Figure Z/AA
Figure Z/AA
Figure Z/AA
Figure Z/AA
Figure Z/AA
Figure Z/AA

91
103
117
140
141
141
175
193
193
361
426
522
606
755
890
940
926
1000
1430
1465
1500
1610

217
251
360
467
492
526
678
899
981
1533
1978
2162
2315
3065
3625
3990
5015
5935
7120
8020
8925
10767

308
354
477
607
633
667
853
1092
1174
1894
2404
2683
2921
3820
4515
4930
5941
6935
8550
9485
10425
12377

User Supplied Enclosures

1

Base Derate Amps are based on nominal
voltage (240, 480 or 600V). If input voltage
exceeds Drive Rating, Drive Output must be
derated. Refer to Figure CC.

2

Rating is at 4 kHz (2 kHz for 224–448
kW/300–600 HP, 500–600V). If carrier
frequencies above 4 kHz are selected, drive
rating must be derated. See Figures A–AA.

3

Drive Ambient Temperature Rating is 40

°

C. If

ambient exceeds 40

°

C, the drive must be

derated. Refer to Figures A–AA.

4

Drive Rating is based on altitudes of 1,000 m
(3,000 ft) or less. If installed at higher altitude,
drive must be derated Refer to Figure BB.

5

Important: Two (2) 725 CFM fans are required
if an open type drive is mounted in a user
supplied enclosure.

6

Not available at time of printing.

Advertising