Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual

Page 38

Advertising
background image

2–28

Installation/Wiring

Figure 2.5
Input Mode Selection & Typical TB3 Connections

19

20

21

22

23

24

25

26

27

28

29

30

Status

Stop/Fault Reset

3

Common

Status

Status

Status

Common

Status

Status

Status

Common

Enable

3

[Input Mode] 1

Factory Default

19

20

21

22

23

24

25

26

27

28

29

30

Start

Stop/Fault Reset

3

Common

Auxiliary

3

Common

Speed Select 2

1

Speed Select 1

1

Common

Enable

3

Jog

7

Stop
Type

2nd

Accel

Digital

Pot Up

Jog

7

Reverse

4

Reverse

4

Reverse

4

Reverse

4

Reverse

4

Reverse

4

Integrator

Reset

6

Speed

Select 3

1

Speed

Select 3

1

2nd

Decel

Digital

Pot Dn

Local

Control

2

Jog

7

Jog

7

Integrator

Reset

6

Speed

Select 3

1

2

3

4

5

6

17

5

18

5

Integrator

Reset

6

PI

Output

Speed

Select 3

1

22

8

Mode

[Input Mode] 2-6, 17, 18, 22

Three-Wire Control with Single-Source Reversing

See Figure 2.6 for Wiring Information

See Figure 2.6 for Wiring Information

ATTENTION:

The JOG function will not operate properly

unless a SCANport option is connected to the drive. To assure

proper JOG function, install at least one of the following:

1201-HAP, 1201-HA1, 1201-HA2, 1336-GM1. Applies to

1305 with firmware FRN 2.01 or earlier and 1336 PLUS with

Language Module 1336S-EN firmware FRN 1.05 or earlier.

!

Note: If this mode is selected, the status of all
inputs can be read at the [Input Status] parameter.
However, only “Stop/Fault Reset” and “Enable” will
have control function.

1

See Speed Select Table.

2

Drive must be stopped to take Local Control. Control by all other
adapters is disabled (except Stop).

3

These inputs must be present before drive will start.

4

Bit 0 of [Direction Mask] must = 1 to allow TB3 direction change.

5

Firmware version 3.01 and Up, Only.

6

Inverted function – voltage resets integrator to zero.

7

See ATTENTION statement on this page.

8

Firmware version 4.01 and Up, Only.

Momentary

Maintained

Advertising