Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual

Page 122

Advertising
background image

5–44

Programming

This group of parameters contains the parameters used to scale, in “User Units”, any drive
parameter for display on the HIM. Two scaled parameter values can be simultaneously
displayed when Process Mode is selected.

Process

Display

[Process 1 Par]

This parameter should be set to the number of the
parameter whose scaled value will be displayed on
Line 1 of the HIM Display Panel.

The maximum process value that can be displayed
is 99,999.99. If this value is exceeded, a character
string of asterisks (****) will appear on the display.

Parameter Number

127

Parameter Type

Read and Write

Display Units / Drive Units

Parameter # / Parameter #

Factory Default

1

[Process 1 Scale]

This value sets the scaling multiplier for
[Process 1 Par]. The displayed value will be:

[Process 1 Par] actual value

x [Process 1 Scale] value

Displayed Value

Parameter Number

128

Parameter Type

Read and Write

Display Units / Drive Units

Numeric / Scale x 100

Factory Default

+1.00

Minimum Value

–327.68

Maximum Value

+ 327.67

[Process 1 Txt 1-8]

Sets the “User Units” description for the value
determined by [Process 1 Par] and [Process 1 Scale].
This 8 character description will be shown on line 1 of
the display. Refer to the Character Map in Appendix A.

Parameter Number(s)

129-136

Parameter Type

Read and Write

Display Units / Drive Units

ASCII Code / ASCII Code

Factory Default

“Volts ”

[Process 2 Par]

This parameter should be set to the number of the
parameter whose scaled value will be displayed on
Line 2 of the HIM Display Panel.

The maximum process value that can be displayed
is 99,999.99. If this value is exceeded, a character
string of asterisks (****) will appear on the display.

Parameter Number

180

Parameter Type

Read and Write

Display Units / Drive Units

Parameter # / Parameter #

Factory Default

54

[Process 2 Scale]

This value sets the scaling multiplier for
[Process 2 Par]. The displayed value will be:

[Process 2 Par] actual value

x [Process 2 Scale] value

Displayed Value

Parameter Number

181

Parameter Type

Read and Write

Display Units / Drive Units

Numeric / Scale x 100

Factory Default

+1.00

Minimum Value

–327.68

Maximum Value

+ 327.67

[Process 2 Txt 1-8]

Sets the “User Units” description for the value
determined by [Process 2 Par] and [Process 2 Scale].
This 8 character description will be shown on line 2 of
the display. Refer to the Character Map in Appendix A.

Parameter Number(s)

182-189

Parameter Type

Read and Write

Display Units / Drive Units

ASCII Code / ASCII Code

Factory Default

“Amps ”

Advertising