Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual

Page 180

Advertising
background image

C–6

CE Conformity

Filter Mounting (continued)

1336 PLUS & FORCE

(Typical Mounting)

Frame G

2

75.0

(2.95)

Mounting Brackets

Typical Connection

to Drive

AC Input Terminals

Typical Bracket

for Stability

831.0

(32.72)

Important: This information represents the
method used to mount 1336-RFB-475, 590 & 670
filters in an Allen-Bradley supplied EMC enclosure. User
supplied EMC enclosures must follow all of the guidelines
shown. Illustrations are only intended to identify structural
mounting points and hardware shapes. You must design and
fabricate steel components based on the actual mounting
configuration, calculated loads and enclosure specifications. Refer to
the PLUS/FORCE User Manual for drive mounting requirements.

Important: A positive electrical bond must be maintained
between the enclosure and filter (including brackets),
fans, and drive. To assure a positive electrical bond,
any paint near all mounting points must be
removed.

Important: Cooling fans are required for proper
drive operation. Refer to the PLUS/FORCE User
Manual for CFM recommendations.

All Dimensions in Millimeters and (Inches)

1

Input power (source to filter) and output power (filter to drive and drive to motor) wiring must be in conduit or have shielding/armor with equivalent attenuation.
Shielding/armor must be bonded to the metal bottom plate. See requirements 6 & 7 on page C–1.

2

Refer to the Filter Selection table on page C–2 for frame references and corresponding catalog numbers.

Advertising