Input fusing – Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual

Page 15

Advertising
background image

2–5

Installation/Wiring

!

ATTENTION: The 1336 PLUS does not provide
input power short circuit fusing. Specifications for the
recommended fuse size and type to provide drive input
power protection against short circuits are provided.
Branch circuit breakers or disconnect switches cannot
provide this level of protection for drive components.

Table 2.A
Maximum Recommended AC Input Line Fuse Ratings (fuses are user supplied)

European
Installations

North American
Installations

Drive Catalog
Number

kW (HP) Rating

200-240V
Rating

380-480V
Rating

500-600V
Rating

The recommended fuse is Class gG,

UL requirements specify

C

CC

1

1336S- _ _ F05, 7

0.37-0.56 (0.5-0.75)

6A

2

3A

2

The recommended fuse is Class gG,
general industrial applications and
motor circuit protection

UL requirements s ecify
that UL Class CC, T or J

1

fuses must be used for all

1336S- _ _ F10

0.75 (1)

10A

2

6A

2

6A

2

motor circuit protection.

BS88 (B iti h St d d) P t 1 & 2 *

fuses must be used for all
drives in this section*.

1336S- _ _ F15

1.2 (1.5)

15A

2

6A

2

BS88 (British Standard) Parts 1 & 2 *,
EN60269-1 Parts 1 & 2 type gG or

drives in this section*.

* Typical designations

1336S- _ _ F20

1.5 (2)

15A

2

10A

2

10A

2

EN60269-1, Parts 1 & 2, type gG or
equivalent should be used for these

* Typical designations

include:

1336S- _ _ F30

2.2 (3)

25A

2

15A

2

15A

2

equivalent should be used for these
drives. Fuses that meet BS88 Parts 1
& 2

t bl f

F

A F

include:

Type CC: KTK FNQ-R

1336S- _ _ F50

3.7 (5)

40A

2

20A

2

20A

2

& 2 are acceptable for Frames A - F.

Type CC: KTK, FNQ-R
Type J:

JKS, LPJ

1336S- _ _ F75

5.5 (7.5)

20A

2

* Typical designations include, but

t b li it d t th f ll

i

Ty e J:

JKS, LPJ

Type T:

JJS, JJN

1336S- _ _ F100

7.5 (10)

30A

2

y

g

may not be limited to the following:

y

1336S- _ _ 007

5.5 (7.5)

40A

20A

15A

Parts 1 & 2: AC, AD, BC, BD, CD,
DD ED EFS EF FF FG GF GG

1336S- _ _ 010

7.5 (10)

50A

30A

20A

DD, ED, EFS, EF, FF, FG, GF, GG,
GH.

1336S- _ _ 015

11 (15)

70A

35A

25A

GH.

1336S- _ _ 020

15 (20)

100A

45A

35A

1336S- _ _ 025

18.5 (25)

100A

60A

40A

1336S- _ _ 030

22 (30)

125A

70A

50A

1336S- _ _ 040

30 (40)

150A

80A

60A

1336S- _ _ 050

37 (50)

200A

100A

80A

1336S- _ _ X060

45 (60)

100A

1336S- _ _ 060

45 (60)

250A

125A

90A

1336S- _ _ 075

56 (75)

300A

150A

110A

1336S- _ _ 100

75 (100)

400A

200A

150A

1336S- _ _ 125

93 (125)

450A

250A

175A

1336S- _ _ X150

112 (150)

250A

1336S- _ _ 150

112 (150)

300A

225A

1336S- _ _ 200

149 (200)

400A

350A

1336S- _ _ 250

187 (250)

450A

400A

1336S- _ _ X300

224 (300)

400A

The recommended fuse is Class gG,

Bussmann FWP/Gould
S

Q

QS

1336S- _ P250

3

187 (250)

450A

3

The recommended fuse is Class gG,
general industrial applications and
motor circuit protection

Bussmann FWP/Gould
Shawmut A-70Q or QS
semiconductor type fuses

1336S- _ _ X250

187 (250)

450A

motor circuit protection.

BS88 (British Standard) Part 4

semiconductor type fuses
must be used for all drives

1336S- _ _ 300

224 (300)

450A

400A

BS88 (British Standard) Part 4,
EN60269-1, Part 4 *, type gG semi-

must be used for all drives
in this section.

1336S- _ P300

3

224 (300)

500A

3

EN60269-1, Part 4 *, type gG semi-
conductor fuses or equivalent should

in this section.

1336S- _ _ 350

261 (350)

500A

450A

conductor fuses or equivalent should
be used for these drives. G Frame
drives require semiconductor fuses

1336S- _ P350

3

261 (350)

600A

3

drives require semiconductor fuses
and should be fused with Part 4 fuses

1336S- _ _ 400

298 (400)

600A

500A

and should be fused with Part 4 fuses.

* Typical designations include but

1336S- _ P400

3

298 (400)

600A

3

* Typical designations include, but

may not be limited to the following:

1336S- _ _ 450

336 (450)

800A

600A

may not be limited to the following:

Part 4: CT ET FE EET FEE RFEE

1336S- _ P450

3

336 (450)

700A

3

Part 4: CT, ET, FE, EET, FEE, RFEE,
FM, FMM.

1336S- _ _ 500

373 (500)

800A

800A

FM, FMM.

1336S- _ _ 600

448 (600)

900A

800A

1

Both fast acting and slow blow are acceptable.

2

Dual element-time delay fuses are required.

3

Fuses are supplied with F Frame drives.

Input Fusing