Lug kits – Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual

Page 22

Advertising
background image

2–12

Installation/Wiring

Table 2.C
TB1 Specifications –
Use 75

°

C Copper wire Only

Drive Frame
Size

Max./Min. Wire Size

1

mm

2

(AWG)

Maximum Torque
N-m (lb.-in.)

A1-A4 (page 2–18)

5.3/0.8 (10/18)

1.81 (16)

B1 (page 2–18)

8.4/0.8 (8/18)

1.81 (16)

B2 (page 2–18)

13.3/0.5 (6/20)

1.70 (15)

C (page 2–18)

26.7/0.8 (3/18)

5.65 (50)

D (page 2–19)

3

127.0/2.1 (250 MCM/14)
67.4/2.1 (00/14)

2

6.00 (52)
6.00 (52)

E (page 2–19)

3

253.0/2.1 (500 MCM/14)

10.00 (87)

F (page 2–20)

3

303.6/2.1 (600 MCM/14)

23.00 (200)

G (page 2–20)

3

303.6/2.1 (600 MCM/14)

23.00 (200)

1

Wire sizes given are maximum/minimum sizes that TB1 will accept – these are not recommendations.

2

Applies to 30 kW (40 HP) 200-240V, 45 & 56 kW (60 & 75 HP) 380-480V, 56 kW (75 HP) 500-600V
drives only.

3

These configurations of TB1 are stud type terminations and require the use of lug type connectors to
terminate field installed conductors. Lug kits are available for use with these configurations. Wire size
used is determined by selecting the proper lug based on the drive catalog number. Refer to Table 2.D.

Lug Kits

D, E, F and G Frame drives have stud type terminals and/or bus
bars/bolts that require standard “crimp type” connectors for cable
termination. Connectors such as T & B Color-Keyed

connectors (or

equivalent) are recommended. The following table shows the lug
selection for one possible cable choice. Connectors for each
installation should be chosen based on desired cable sizes, the
application requirements and all applicable national, state and local
codes. See the minimum/maximum values for wire size per Table
2.C.