Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual

Page 107

Advertising
background image

5–29

Programming

This group of parameters allows configuring, viewing and clearing drive faults.

Faults

[Fault Buffer 0-3]

These parameters store the last (4) faults that occur.

Parameter Number

86-89

Parameter Type

Read and Write

Factory Default

None

Units

Display Drive

“0” 0

Last Fault

“1” 1

Fault from Buffer 0

“2” 2

Fault from Buffer 1

“3” 3

Fault from Buffer 2

[Clear Fault]

Selecting “Clear Fault” and pressing Enter will clear
any faults and return the drive to ready status.

Parameter Number

51

Parameter Type

Read and Write

Factory Default

“Ready”

Units

Display Drive

“Ready” 0

“Clear Fault” 1

[Cur Lim Trip En]

This setting determines the drive response when the
hardware current limit is exceeded. The current limit
is approximately 180% of [Rated VT Amps] for B
Frame drives & up, and approximately 250% of
[Rated VT Amps] for A Frame drives.

Parameter Number

82

Parameter Type

Read and Write

Factory Default

“Disabled”

Units

Display Drive

“Disabled” 0

No Fault Generated – C.L. Activated

“Enabled” 1

Diag C Lim Flt Generated

[Shear Pin Fault]–Firmware 4.01 & later

Enabling this parameter allows the drive to generate
a Shear Pin Fault (F63) if the output amps exceed
the programmed software current limit value in
[Current Limit].

Parameter Number

226

Parameter Type

Read and Write

Factory Default

“Disabled”

Units

Display Drive

“Disabled” 0

No Fault Generated

“Enabled” 1

Fault Generated

[Motor OL Fault] –Firmware 4.01 & later

This parameter enables or disables the motor
overload protection feature of the drive.

Parameter Number

201

Parameter Type

Read and Write

Factory Default

“Enabled”

Units

Display Drive

“Disabled” 0

No Fault Generated

“Enabled” 1

Fault Generated

[Line Loss Fault]

This setting determines how a 15% drop in DC Bus
voltage will affect drive operation. See following
diagram.

Parameter Number

40

Parameter Type

Read and Write

Factory Default

“Disabled” (“Enabled” frn < 4.01)

Units

Display Drive

“Disabled” 0

No Fault Generated

“Enabled” 1

Power Loss Fault Generated

Advertising