[IR Drop Volts] – Firmware 4.01 & later

Used in Sensorless Vector mode only – Sets the
value of volts dropped across the resistance of the
motor stator. If set to zero, the drive will use an
internal value based on motor F.L.A. and rated
voltage. Some motors (i.e. 6 pole, special, etc.) may
be particularly sensitive to the adjustment of this
parameter. Refer to the tuning procedure in Chapter
4 for further information.

Parameter Number

194

Parameter Type

Read and Write

Display Units / Drive Units

1 Volt / 4096 = Drive Rated Volts

Factory Default

0 Volts

Minimum Value

0 Volts

Maximum Value

25% of Drive Rated Volts

[Flux Up Time] – Firmware 4.01 & later

Sets the amount of time the drive will use to try and
achieve full motor stator flux. When a Start
command is issued, DC current at current limit level
is used to build stator flux before accelerating.

Parameter Number

200

Parameter Type

Read and Write

Display Units / Drive Units

0.1 Sec / Sec x 10

Factory Default

0.0 Sec

Minimum Value

0.0 Sec

Maximum Value

5.0 Sec

[Start Boost]

This parameter sets the DC start boost level for
acceleration when [DC Boost Select] is set to “Fixed”
or “Full Custom.”

Parameter Number

48

Parameter Type

Read and Write

Display Units / Drive Units

1 Volt / 4096 = Drive Rtd Volts

Factory Default

0 Volts

Minimum Value

0 Volts

Maximum Value

9.5% of Drive Rated Voltage

[Run Boost]

This parameter sets the DC boost level for constant
speed level when [DC Boost Select] is set to “Fixed”.

Parameter Number

83

Parameter Type

Read and Write

Display Units / Drive Units

1 Volt / 4096 = Drive Rtd Volts

Factory Default

0 Volts

Minimum Value

0 Volts

Maximum Value

9.5% of Drive Rated Voltage

[Boost Slope] – Firmware 4.01 & later

Sets the slope of the volts/Hertz curve from zero
Hertz to the intersect point (see Fixed boost diagram
above). The slope is determined by multiplying:
Run Boost x Boost Slope = A
Start Boost x Boost Slope = B.

Parameter Number

169

Parameter Type

Read and Write

Display Units / Drive Units

None

Factory Default

1.5

Minimum Value

1.0

Maximum Value

8.0

[Break Voltage]

Sets the voltage the drive will output at [Break
Frequency]. Combined with [Break Frequency], this
parameter determines the volts-per-Hertz pattern
between 0 and [Break Frequency].

Parameter Number

50

Parameter Type

Read and Write

Display Units / Drive Units

1 Volt / 4096 = Drive Rtd Volts

Factory Default

25% of Drive Rated Voltage

Minimum Value

0 Volts

Maximum Value

50% of Drive Rated Voltage

[Break Frequency]

This parameter sets a midpoint frequency on a
custom volts-per-Hertz curve. Combined with [Break
Voltage], this value determines the volts-per-Hertz
ratio between 0 and [Break Frequency].

Parameter Number

49

Parameter Type

Read and Write

Display Units / Drive Units

1 Hertz / Hertz x 10 (x 1 frn < 4.01)

Factory Default

25% of [Maximum Freq]

Minimum Value

0 Hz

Maximum Value

120 Hz

Important: Please note the resolution change with Frn 4.01.