Installation/Wiring

The 480 or 600V (depending on input voltage to drive) output
terminal block (TB9) is only available on F Frame Drives. This
terminal block provides a three-phase, high voltage connection from
the load side of the AC input line fuses. Normally this connection is
used to power an external control transformer (user supplied) or
other auxiliary circuit. Refer to Figure 2.1 for location.

Important:

Depending on the circuitry connected, additional fusing
may be required.

!

ATTENTION: The installation of auxiliary circuits
must comply with the national codes and standards
(NEC, VDE, BSA, etc.) and local codes regarding wire
type, conductor sizes, branch circuit protection and
disconnect devices. Failure to do so may result in
personal injury and/or equipment damage.

The auxiliary circuit can be utilized to a maximum current capacity
of 8 amperes RMS.

The maximum and minimum wire size accepted by TB9 is 4.0 and
0.8 mm

2

(12 and 18 AWG). Use Copper wire Only with a minimum

temperature rating of 75

°

C. Maximum torque is 0.90-1.81 N-m

(8-16 lb.-in.).

Important:

If the Control Interface Board is being installed, Main
Control Board jumpers at pins 3 & 4 and 17 & 18 of J4
(J7 on B Frame & up drives) must be removed and the
proper [Input Mode] selected. If this board is removed,
these jumpers must be reinstalled and the [Input Mode]
parameter must be programmed to “1.”

Figure 2.7
Jumper Locations

LANGUAGE MODULE

ALLEN-BRADLEY

LANGUAGE MODULE

ALLEN-BRADLEY

JOG

ES

C

SE

L

JOG

ES

C

SE

L

J7

J4

Frames

1

A1 - A4

Frames

1

B - G

1

Refer to page 1–1 for frame reference classifications.

Auxiliary Output – TB9

Interface Board
Installation and Removal