Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual

Page 70

Advertising
background image

4–6

Start-Up

or

12. Setting Frequency Command.

A. From the Status Display, press the

Enter key (or any key). “Choose
Mode” will be displayed.

B. Press the Increment key until

“Display” is shown.

C. Press Enter.

D. Press the Decrement key until

“Metering” is displayed.

E. Press Enter.

F. Press the Increment key until “Freq

Command” is displayed.

G. If the frequency command is a value

other than zero, use the speed source
(digital, analog pot, etc.) to set the
command to zero.

H. After the command has been set to

zero, press the ESCape key until the
Status Display is shown.

Stopped

+0.00 Hz

Choose Mode
Program

Metering

Setup

Output Voltage
0 Vlts

Freq Command
+0.00 Hz

Choose Mode
Display

or

13. Verifying Minimum and Maximum

Frequency Settings.

A. Press the Start key. The drive should

output zero Hz. which is the factory
default value for the [Minimum Freq]
parameter. The Status Display should
indicate “At Speed” and the actual
frequency (+0.00 Hz.).

If the drive does not start, check bit 12
(Voltage Check) of the [Drive Alarm]
parameter. If the bit is “1,” the drive
terminal voltage is preventing the drive
from starting. Normally this is caused
by IGBT leakage current. To bypass
this alarm, program [Flying Start En] to
“Track Volts,” then start the drive.

B. With the drive still running, use the

speed source to command maximum
speed. The drive should ramp to
[Maximum Freq].

At Speed

+60.00 Hz

Accelerating

+29.62 Hz

At Speed
+0.00 Hz