4–5

Start-Up

or

or

10. Set [Maximum Freq] and [Maximum

Voltage] parameters to correct values
(typically line voltage/frequency). Set
[Base Voltage] and [Base Frequency]
parameters to the motor nameplate values.

A. From the Status Display, press the

Enter key (or any key). “Choose
Mode” will be displayed.

B. Press the Increment (or Decrement)

key until “Program” is displayed.

C. Press Enter.

D. Press the Increment key until “Setup”

is displayed.

E. Press Enter.

F. Press the Increment or Decrement keys

until “Maximum Freq” is displayed.
Press SELect. The first character of
line 2 will now flash.

G. Use the Increment/Decrement keys to

display the first digit, then press Enter.
Repeat for remaining digits.

H. Repeat the above steps to program the

remaining parameters. In firmware
versions 4.01 & up, the remaining
parameters are located in the Motor
Control group.

I. Press the ESCape key (3 times) to

return to the Status Display.

Choose Mode
EEProm

Stopped

+0.00 Hz

Choose Mode
Program

Metering

Setup

Input Mode
1

Maximum Freq
60

Sensorless Vector or V/Hz

Choose

11. Sensorless Vector or V/Hz operation.

Firmware Version 4.01 & Up Only

Sensorless Vector or Volts/Hertz operation
is selectable via [Control Select]. Vector
operation is the default. If V/Hz operation
is desired, reprogram [Control Select]
using the steps above as a programming
guide. Refer to page 5–51.