Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual
Page 132
5–54
Programming
This group lists all the parameters currently installed in your drive in numerical order. Refer
to the Appendix at the back of this manual for an alpha/numeric listing of all parameters.
Linear List
1336 PLUS Adjustable Frequency AC Drives with a Firmware
Revision Number (FRN) of “5.xx.” have the following additional
parameters:
[Power Dip Restart]
This parameter is only used with the two–wire
control mode. If enabled, a 20 ms delay is added to
the Start command when the Stop and Start
commands are applied simultaneously following a
power loss condition.
Parameter Number
241
Parameter Type
Read and Write
Factory Default
“Disabled”
Units
Display Drive
“Disabled” 0
“Enabled” 1
[Stability Gain]
This parameter adjusts the gain of the torque
component of current to adjust for possible current
instability in certain motors caused by variations in
design. Increasing this value to the correct setting
for a particular motor will stabilize torque pulsations
in the motor.
Important: Setting this value too high may cause
additional instability. It should be set for the lowest
value that eliminates the instability.
Parameter Number
246
Parameter Type
Read and Write
Display Units / Drive Units
None
Factory Default
0
Minimum Value
0
Maximum Value
16