Dig out torque, Analog input configuration – Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual

Page 105

Advertising
background image

5–27

Programming

[Dig Out Torque]

This value sets the trip point for the output contact at
TB2 terminals 10 & 11 when [Digital Out Sel] is set
to “At Torque”. The contact will be closed when
above this value.

Parameter Number

161

Parameter Type

Read and Write

Display Units / Drive Units

0.1 Amps / 4096 = Rated Torque Amps

Factory Default

0.0 Amps

Minimum Value

0.0 Amps

Maximum Value

200% of [Rated Amps]

[Set 0-10 Vlt Lo] – Firmware 4.01 & later

Sets the percentage of the 0-10 volt input that
represents [Minimum Freq].

Parameter Number

237

Parameter Type

Read and Write

Display Units / Drive Units

0.1 % / 4096 = 100%

Factory Default

0.0 %

Minimum Value

–300.0 %

Maximum Value

+300.0 %

[Set 0-10 Vlt Hi] – Firmware 4.01 & later

Sets the percentage of the 0-10 volt input that
represents [Maximum Freq].

Parameter Number

238

Parameter Type

Read and Write

Display Units / Drive Units

0.1 % / 4096 = 100%

Factory Default

100.0 %

Minimum Value

–300.0 %

Maximum Value

+300.0 %

[Set 4-20 mA Lo] – Firmware 4.01 & later

Sets the percentage of the 4-20 mA input that
represents [Minimum Freq].

Parameter Number

239

Parameter Type

Read and Write

Display Units / Drive Units

0.1 % / 4096 = 100%

Factory Default

0.0 %

Minimum Value

–300.0 %

Maximum Value

+300.0 %

[Set 4-20 mA Hi] – Firmware 4.01 & later

Sets the percentage of the 4-20 mA input that
represents [Maximum Freq].

Parameter Number

240

Parameter Type

Read and Write

Display Units / Drive Units

0.1 % / 4096 = 100%

Factory Default

100.0 %

Minimum Value

–300.0 %

Maximum Value

+300.0 %

Input Volts

Output Hertz

Offset

Invert

Normal/Default

0

8

10

6

4

2

0

48

42

54

60

36

30

24

18

12

6

Input Volts

Output Hertz

0

8

10

6

4

2

0

48

42

54

60

36

30

24

18

12

6

Input Volts

Output Hertz

0

8

10

6

4

2

0

48

42

54

60

36

30

24

18

12

6

Analog Input Configuration

Examples shown are for 0-10V. Settings for 4-20 mA are similar.

[Minimum Freq] = 0 Hz
[Maximum Freq] = 60 Hz
[Set 0-10 Vlt Lo] = 20%
[Set 0-10 Vlt Hi] = 100%

2-10 volt input signal provides 0-60 Hz output, resulting
in a 2 volt offset in the speed command.

[Minimum Freq] = 0 Hz
[Maximum Freq] = 60 Hz
[Set 0-10 Vlt Lo] = 100%
[Set 0-10 Vlt Hi] = 0%

Maximum input (100% of 10V=10V) represents a
minimum frequency of 0 Hz & minimum input (0% of
10V=0V) represents a maximum frequency of 60 Hz.

[Minimum Freq] = 0 Hz
[Maximum Freq] = 60 Hz
[Set 0-10 Vlt Lo] = 0%
[Set 0-10 Vlt Hi] = 100%

Minimum input (0% of 10V=0V) represents minimum
frequency of 0 Hz and maximum input (100% of
10V=10V) represents maximum frequency of 60 Hz.

I/O Config