Derating guidelines – Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual

Page 145

Advertising
background image

A–5

Specifications and Supplemental Information

Drive ratings can be affected by a number of factors. If more than
one factor exists, derating percentages must be multiplied. For
example, if a 42 Amp drive (B025) running at 8 kHz is installed at a
2,000 m (6,600 ft.) altitude and has a 2% high input line voltage, the
actual amp rating will be:

42 x 94% Altitude Derate x 96% High Line Derate = 37.9 Amps.

AMBIENT TEMPERATURE / CARRIER FREQUENCY

Standard Rating for Enclosed Drive in
40

°

C Ambient & Open Drive in 50

°

C Ambient.

Derating Factor for Enclosed Drive in
Ambient between 41

°

C & 50

°

C.

% of Drive

Rated Amps

Figure B
1336S-A010 and B020

Carrier Frequency in kHz

4

2

6

8

92%

98%

94%

90%

96%

100%

Figure C
1336S-B025

Carrier Frequency in kHz

4

2

6

8

84%

96%

88%

80%

92%

100%

% of Drive

Rated Amps

Figure D
1336S-A015 and B030

Carrier Frequency in kHz

4

2

6

8

70%

85%

90%

95%

75%

65%

80%

100%

% of Drive

Rated Amps

Figure E
1336S-B040 and BX040

Carrier Frequency in kHz

2

4

6

88%

90%

98%

92%

94%

86%

96%

100%

% of Drive

Rated Amps

Carrier Frequency in kHz

6

2

4

10

8

92%

98%

94%

90%

96%

100%

% of Drive

Rated Amps

Figure A
AQF05-AQF50 and BRF05-BRF100

Derating Guidelines