Derating guidelines – Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual
Page 145
A–5
Specifications and Supplemental Information
Drive ratings can be affected by a number of factors. If more than
one factor exists, derating percentages must be multiplied. For
example, if a 42 Amp drive (B025) running at 8 kHz is installed at a
2,000 m (6,600 ft.) altitude and has a 2% high input line voltage, the
actual amp rating will be:
42 x 94% Altitude Derate x 96% High Line Derate = 37.9 Amps.
AMBIENT TEMPERATURE / CARRIER FREQUENCY
Standard Rating for Enclosed Drive in
40
°
C Ambient & Open Drive in 50
°
C Ambient.
Derating Factor for Enclosed Drive in
Ambient between 41
°
C & 50
°
C.
% of Drive
Rated Amps
Figure B
1336S-A010 and B020
Carrier Frequency in kHz
4
2
6
8
92%
98%
94%
90%
96%
100%
Figure C
1336S-B025
Carrier Frequency in kHz
4
2
6
8
84%
96%
88%
80%
92%
100%
% of Drive
Rated Amps
Figure D
1336S-A015 and B030
Carrier Frequency in kHz
4
2
6
8
70%
85%
90%
95%
75%
65%
80%
100%
% of Drive
Rated Amps
Figure E
1336S-B040 and BX040
Carrier Frequency in kHz
2
4
6
88%
90%
98%
92%
94%
86%
96%
100%
% of Drive
Rated Amps
Carrier Frequency in kHz
6
2
4
10
8
92%
98%
94%
90%
96%
100%
% of Drive
Rated Amps
Figure A
AQF05-AQF50 and BRF05-BRF100
Derating Guidelines