6–5

Troubleshooting

Name & Fault #

Action

Description

Phase V Fault
39

A phase to ground fault has
been detected between the
drive and motor in this phase.

Check the wiring between the drive
and motor. Check motor for
grounded phase.

Phase W Fault
40

A phase to ground fault has
been detected between the
drive and motor in this phase.

Check the wiring between the drive
and motor. Check motor for
grounded phase.

P Jump Err Flt
37

Reserved for future use.

Poles Calc Flt
50

Generated if the calculated
value of [Motor Poles] is less
than 2 or greater than 32.

Check [Motor NP RPM] and [Motor
NP Hertz] programming.

Power Loss Fault
03

DC bus voltage remained
below 85% of nominal for
longer than 500ms. [Line Loss
Fault] parameter is set to
“enabled.”

Monitor the incoming AC line for
low voltage or line power
interruption.

Power Mode Fault
26

The internal power mode
variable received an incorrect
value.

Check all connections to the
Control Board. Replace the board,
Language Module or complete
drive as required.

Power Overload
64

The drive rating of 150% for 1
minute has been exceeded.

Reduce load.

Power Test Flt
46

The internal power mode
variable received an incorrect
value.

Check all connections to the
Power/Driver Board. Replace the
board or complete drive as needed.

Precharge Fault
19

The precharge device was
open 20ms after the end of a
line loss condition or the bus
charging alarm remains on for
20 seconds (precharge did not
complete).

See Chapter 1 for frame
definitions.
1.Frames A1, A2, A3 – Check the

precharge circuit. Replace the
precharge NTC or complete
drive as needed.

2. Frame B – Check the precharge

circuit. Replace the precharge
transistor, Power Driver Board or
complete drive as required.

3. All larger frames – Check the

precharge circuit. Replace the
input SCRs, SCR Firing Board,
Power Driver Board or complete
drive as needed.

Precharge Open
56

The precharge circuit was
commanded to close, but was
detected to be open.

See page 1–1 for frame definitions.
1.Frames A1, A2, A3 – Check the

precharge circuit. Replace the
precharge NTC or complete
drive as needed.

2. Frame B – Check the precharge

circuit. Replace the precharge
transistor, Power Driver Board or
complete drive as required.

3. All larger frames – Check the

precharge circuit. Replace the
input SCRs, SCR Firing Board,
Power Driver Board or complete
drive as needed.