Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual

Page 39

Advertising
background image

2–29

Installation/Wiring

Run Forward/Stop

4

Stop/Fault Reset

3

Common

Run Reverse/Stop

4

Auxiliary

3

Common

Speed Select 2

1

Speed Select 1

1

Common

Enable

3

Local

Control

2

Stop
Type

2nd

Accel

Digital

Pot Up

Local

Control

2

Speed

Select 3

1

Speed

Select 3

1

Speed

Select 3

1

2nd

Decel

Digital

Pot Dn

Stop
Type

12

13

14

15

16

Local

Control

2

Integrator

Reset

6

Integrator

Reset

6

20

5

Jog

7

21

8

PI

Output

24

8

Mode

[Input Mode] 12-16, 20, 21, 24

Two-Wire Control, Single-Source Control

19

20

21

22

23

24

25

26

27

28

29

30

Start

Stop/Fault Reset

3

Common

Auxiliary

3

Common

Speed Select 1

1

Common

Enable

3

Forward

4

Forward

4

Digital

Pot Dn

Forward

4

2nd

Accel

Jog

7

Speed

Select 3

1

Speed

Select 3

1

Digital

Pot Up

1st

Decel

[Input Mode] 7-11, 19, 23

Three-Wire Control with Multi-Source Reversing

Reverse

4

Reverse

4

Digital

Pot Up

Reverse

4

1st

Accel

7

8

9

10

11

Mode

Speed

Select 2

1

Speed

Select 2

1

Speed

Select 2

1

Digital

Pot Dn

2nd

Decel

Forward

4

Integrator

Reset

6

Reverse

4

19

5

Speed

Select 2

1

Forward

4

Integrator

Reset

6

Reverse

4

23

8

PI

Output

19

20

21

22

23

24

25

26

27

28

29

30

See Figure 2.6 for Wiring Information

See Figure 2.6 for Wiring Information

Momentary

Maintained

See ATTENTION

statement below

!

!

Two wire control uses maintained Run contacts that act as
both Run (closed) and Stop (open) devices. Opening the Stop
contact (terminal 20) will stop the drive. If this contact is
reclosed, any fault will be reset. If a valid Start command is
still present, the drive will restart.

If a three wire device (i.e. HIM) is also used, pressing the HIM
Stop key will also stop the drive. Releasing the Stop key will
clear any faults that are present, but the drive will not restart
without cycling the Start contact.

ATTENTION:

The JOG function will not operate properly

unless a SCANport option is connected to the drive. To assure

proper JOG function, install at least one of the following:

1201-HAP, 1201-HA1, 1201-HA2, 1336-GM1. Applies to

1305 with firmware FRN 2.01 or earlier and 1336 PLUS with

Language Module 1336S-EN firmware FRN 1.05 or earlier.

!