background image

A–2

Specifications and Supplemental Information

Electrical

Input Data

Voltage Tolerance:

–10% of minimum, +10% of maximum.

Frequency Tolerance:

48-62 Hz.

Input Phases:

Three-phase input provides full rating for all drives.
Single-phase operation is possible for A & B Frame drives
at a derating of 50%.

Displacement Power Factor

A1-A3 Frame Drives:

0.80 standard, 0.95 with optional inductor.

A4 Frame & Up Drives:

0.95 standard.

Efficiency:

97.5% at rated amps, nominal line volts.

Max. Short Circuit Current Rating: 200,000A rms symmetrical, 600 volts (when used with AC

input line fuses specified in Chapter 2).

Control

Method:

Sine coded PWM with programmable carrier frequency. Ratings
apply to all drives (refer to the Derating Guidelines on page A–5).

A Frame Drives

2-10 kHz. Drive rating based on 4 kHz (see pg. 1–1 for frame info).

B Frame Drives

2-8 kHz. Drive rating based on 4 kHz (see pg. 1–1 for frame info).

C & D Frame Drives

2-6 kHz. Drive rating based on 4 kHz (see pg. 1–1 for frame info).

E Frame Drives & Up

2-6 kHz. Drive rating based on 2 kHz (see pg. 1–1 for frame info).

Output Voltage Range:

0 to rated voltage.

Output Frequency Range:

0 to 400 Hz.

Frequency Accuracy

Digital Input:

Within

±

0.01% of set output frequency.

Analog Input:

Within

±

0.4% of maximum output frequency.

Selectable Motor Control:

Sensorless Vector with full tuning. Standard V/Hz with full custom
capability.

Accel/Decel:

Two independently programmable accel and decel times. Each
time may be programmed from 0 - 3600 seconds

1

in 0.1 second

increments

2

.

Intermittent Overload:

Constant Torque – 150% of rated output for 1 minute.
Variable Torque – 115% of rated output for 1 minute.

Current Limit Capability:

Proactive Current Limit programmable from 20 to 160% of rated
output current. Independently programmable proportional and in-
tegral gain.

Inverse Time Overload Cap. Class 10 protection with speed sensitive response. Investigated by

U.L. to comply with N.E.C. Article 430. U.L. File E59272, volume 4/6.

1

600 seconds with Firmware Versions before 4.01.

2

0.1 second increments using a HIM or 0.01 with serial communications.

Input/Output Ratings

Each 1336 PLUS Drive has constant and variable torque capabilities. The
listings on the next page provide input & output current and kVA ratings.

Note: Drive ratings are at nominal values. See Derating Guidelines
on page A–5.