Latched alarms, Input status, Freq source – Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual

Page 113: Freq command, Drive direction

Advertising
background image

5–35

Programming

[Latched Alarms]

This parameter “stores” the [Drive
Alarm] indications (see above). Bits
will remain set (high/1), even if the
alarm condition no longer exists.
The bit(s) must be programmed to
zero to release the stored
indications.

With drive software versions above
2.00 and a Series A (version 3.0) or
Series B HIM, a Status description
(bit ENUM) is displayed on line 1.

Parameter Number

205

Parameter Type

Read Only

Bus Charging

Regenerating Current Limit

Regenerating Voltage Limit

Line Loss In Progress

Motor Stalled

Ground Warning

Bit 15

Bit 13 Bit 12 Bit 11 Bit 10 Bit 9

Bit 8

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Mtr Overload

Unused

Bit 14

Hardware Current Limit

Motoring Current Limit

Motor OL Trip

Auto Reset

Voltage Check

Heatsink Temp

Auxiliary Input

4-20 mA Loss

[Input Status]

This parameter displays the on/off status of inputs
1-8 at TB3 if an optional interface card is installed.

With drive software versions above 2.00 and a
Series A (version 3.0) or Series B HIM, a Status
description (bit ENUM) is displayed on line 1.

Parameter Number

55

Parameter Type

Read Only

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Input 1 – TB3-19
Input 2 – TB3-20
Input 4 – TB3-23
Input 3 – TB3-22
Input 5 – TB3-24
Input 6 – TB3-26
Input 8 – TB3-28
Input 7 – TB3-27

[Freq Source]

This parameter displays the frequency source
currently commanding the drive.

Parameter Number

62

Parameter Type

Read Only

Factory Default

None

Units

Display Drive

“Adapter 1-6” 6-11

“Preset 1-7” 12-18

“Use Last” 0

“Remote Pot” 1

“0-10 Volt” 2

“4-20 mA” 3

“Pulse Ref” 4

“MOP” 5

[Freq Command]

This parameter displays the frequency that the drive
is commanded to output. This command may come
from any one of the frequency sources selected by
[Freq Select 1] or [Freq Select 2].

Parameter Number

65

Parameter Type

Read Only

Display Units / Drive Units

0.01 Hertz / 32767 = Maximum Freq Forward

Factory Default

None

Minimum Value

–400.00 Hz

Maximum Value

+ 400.00 Hz

[Drive Direction]

This parameter displays the commanded running
direction.

Parameter Number

69

Parameter Type

Read Only

Factory Default

None

Units

Display Drive

“Forward” 0

“Reverse” 1

Diagnostics