Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual
Page 131
5–53
Programming
[Base Voltage]
This value should be set to the motor nameplate
rated voltage.
Parameter Number
18
Parameter Type
Read and Write
Display Units / Drive Units
1 Volt / 4096 = Drive Rtd Volts
Factory Default
Drive Rated Volts
Minimum Value
25% of Drive Rated Voltage
Maximum Value
120% of Drive Rated Voltage
[Base Frequency]
This value should be set to the motor nameplate
rated frequency.
Parameter Number
17
Parameter Type
Read and Write
Display Units / Drive Units
1 Hertz / Hertz x 10 (x 1 frn < 4.01)
Factory Default
60 Hz
Minimum Value
25 Hz
Maximum Value
400 Hz
Important: Please note the resolution change with Frn 4.01.
[Maximum Voltage]
This parameter sets the highest voltage the drive will
output.
Parameter Number
20
Parameter Type
Read and Write
Display Units / Drive Units
1 Volt / 4096 = Drive Rtd Volts
Factory Default
Drive Rated Volts
Minimum Value
25% of Drive Rated Voltage
Maximum Value
120% of Drive Rated Voltage
Motor Control