5–53

Programming

[Base Voltage]

This value should be set to the motor nameplate
rated voltage.

Parameter Number

18

Parameter Type

Read and Write

Display Units / Drive Units

1 Volt / 4096 = Drive Rtd Volts

Factory Default

Drive Rated Volts

Minimum Value

25% of Drive Rated Voltage

Maximum Value

120% of Drive Rated Voltage

[Base Frequency]

This value should be set to the motor nameplate
rated frequency.

Parameter Number

17

Parameter Type

Read and Write

Display Units / Drive Units

1 Hertz / Hertz x 10 (x 1 frn < 4.01)

Factory Default

60 Hz

Minimum Value

25 Hz

Maximum Value

400 Hz

Important: Please note the resolution change with Frn 4.01.

[Maximum Voltage]

This parameter sets the highest voltage the drive will
output.

Parameter Number

20

Parameter Type

Read and Write

Display Units / Drive Units

1 Volt / 4096 = Drive Rtd Volts

Factory Default

Drive Rated Volts

Minimum Value

25% of Drive Rated Voltage

Maximum Value

120% of Drive Rated Voltage

Motor Control