Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual

Page 26

Advertising
background image

2–16

Installation/Wiring

Table 2.E
Maximum Motor Cable Length Restrictions in meters (feet) – 380V-480V Drives

1

No External Devices

w/ 1204-TFB2 Term.

w/ 1204-TFA1 Terminator

Reactor at Drive

2

Motor

Motor

Motor

Motor

A

B

1329

1329R/L

A or B

1329

A

B

1329

A

B or 1329

Drive

Drive kW

Motor kW

Any

Any

Any

Any

Cable Type

Any

Cable Type

Cable Type

Any

Any

Any

Drive
Frame

Drive kW
(HP)

Motor kW
(HP)

Any
Cable

Any
Cable

Any
Cable

Any
Cable

7

Shld.

3

Unshld.

Any
Cable

Shld.

3

Unshld.

Shld.

3

Unshld.

Any
Cable

Any
Cable

Any
Cable

A1

0.37 (0.5)

0.37 (0.5)

12.2
(40)

33.5
(110)

91.4
(300)

91.4
(300)

30.5
(100)

61.0
(200)

30.5
(100)

61.0
(200)

91.4
(300)

22.9
(75)

182.9
(600)

0.75 (1)

0.75 (1)

12.2
(40)

33.5
(110)

91.4
(300)

91.4
(300)

30.5
(100)

30.5
(100)

30.5
(100)

30.5
(100)

91.4
(300)

22.9
(75)

182.9
(600)

0.37 (0.5)

12.2
(40)

33.5
(110)

91.4
(300)

91.4
(300)

Use 1204-TFA1

30.5
(100)

61.0
(200)

30.5
(100)

61.0
(200)

91.4
(300)

22.9
(75)

182.9
(600)

A2

1.2 (1.5)

1.2 (1.5)

12.2
(40)

33.5
(110)

91.4
(300)

91.4
(300)

30.5
(100)

30.5
(100)

61.0
(200)

61.0
(200)

91.4
(300)

22.9
(75)

182.9
(600)

0.75 (1)

12.2
(40)

33.5
(110)

91.4
(300)

91.4
(300)

30.5
(100)

30.5
(100)

61.0
(200)

61.0
(200)

91.4
(300)

22.9
(75)

182.9
(600)

0.37 (0.5)

12.2
(40)

33.5
(110)

114.3
(375)

121.9
(400)

30.5
(100)

30.5
(100)

61.0
(200)

61.0
(200)

121.9
(400)

22.9
(75)

182.9
(600)

1.5 (2)

1.5 (2)

7.6
(25)

12.2
(40)

91.4
(300)

91.4
(300)

91.4
(300)

91.4
(300)

91.4
(300)

30.5
(100)

30.5
(100)

91.4
(300)

61.0
(200)

91.4
(300)

22.9
(75)

182.9
(600)

1.2 (1.5)

7.6
(25)

12.2
(40)

114.3
(375)

182.9
(600)

91.4
(300)

182.9
(600)

182.9
(600)

30.5
(100)

30.5
(100)

91.4
(300)

61.0
(200)

182.9
(600)

22.9
(75)

182.9
(600)

0.75 (1)

7.6
(25)

12.2
(40)

114.3
(375)

182.9
(600)

182.9
(600)

182.9
(600)

182.9
(600)

30.5
(100)

30.5
(100)

91.4
(300)

61.0
(200)

182.9
(600)

22.9
(75)

182.9
(600)

0.37 (0.5)

7.6
(25)

12.2
(40)

114.3
(375)

182.9
(600)

182.9
(600)

182.9
(600)

182.9
(600)

30.5
(100)

30.5
(100)

91.4
(300)

61.0
(200)

182.9
(600)

22.9
(75)

182.9
(600)

2.2 (3)

2.2 (3)

7.6
(25)

12.2
(40)

91.4
(300)

91.4
(300)

182.9
(600)

182.9
(600)

182.9
(600)

22.9
(75)

182.9
(600)

1.5 (2)

7.6
(25)

12.2
(40)

114.3
(375)

182.9
(600)

182.9
(600)

182.9
(600)

182.9
(600)

22.9
(75)

182.9
(600)

0.75 (1)

7.6
(25)

12.2
(40)

114.3
(375)

182.9
(600)

182.9
(600)

182.9
(600)

182.9
(600)

22.9
(75)

182.9
(600)

0.37 (0.5)

7.6
(25)

12.2
(40)

114.3
(375)

182.9
(600)

182.9
(600)

182.9
(600)

182.9
(600)

22.9
(75)

182.9
(600)

A3

3.7 (5)

3.7 (5)

7.6
(25)

12.2
(40)

114.3
(375)

Note

For

182.9
(600)

182.9
(600)

182.9
(600)

22.9
(75)

182.9
(600)

2.2 (3)

7.6
(25)

12.2
(40)

114.3
(375)

For

applications/

installations

using new

182.9
(600)

182.9
(600)

182.9
(600)

22.9
(75)

182.9
(600)

1.5 (2)

7.6
(25)

12.2
(40)

114.3
(375)

using new

motors, no

restrictions in

182.9
(600)

182.9
(600)

182.9
(600)

22.9
(75)

182.9
(600)

0.75 (1)

7.6
(25)

12.2
(40)

114.3
(375)

restrictions in

lead length

due to

l

182.9
(600)

182.9
(600)

182.9
(600)

U

1204 TFB2

22.9
(75)

182.9
(600)

0.37 (0.5)

7.6
(25)

12.2
(40)

114.3
(375)

due to

voltage

reflection are

necessary

182.9
(600)

182.9
(600)

182.9
(600)

Use 1204-TFB2

22.9
(75)

182.9
(600)

A4

5.5-7.5
(7.5-10)

5.5-7.5
(7.5-10)

7.6
(25)

12.2
(40)

114.3
(375)

necessary.

You should

observe

182.9
(600)

182.9
(600)

182.9
(600)

24.4
(80)

182.9
(600)

B

5.5-22
(7.5-30)

5.5-22
(7.5-30)

7.6
(25)

12.2
(40)

114.3
(375)

observe

standard

practices for

voltage drop

182.9
(600)

182.9
(600)

182.9
(600)

24.4
(80)

182.9
(600)

C

30-45
(X40-X60)

30-45
(40-60)

7.6
(25)

12.2
(40)

114.3
(375)

voltage drop,

cable

capacitance,

182.9
(600)

182.9
(600)

182.9
(600)

76.2
(250)

182.9
(600)

D

45-112
(60-X150)

45-112
(60-150)

12.2
(40)

30.5
(100)

114.3
(375)

ca acitance,

and other

issues.

182.9
(600)

182.9
(600)

182.9
(600)

61.0
(200)

91.4
(300)

E

112-187
(150-250)

112-224
(150-300)

12.2
(40)

53.3
(175)

114.3
(375)

For retrofit

situations,

h k ith

182.9
(600)

182.9
(600)

182.9
(600)

182.9
(600)

182.9
(600)

F

187-336
(250-450)

187-336
(250-450)

18.3
(60)

53.3
(175)

114.3
(375)

,

check with

the motor

manufacturer

182.9
(600)

182.9
(600)

182.9
(600)

182.9
(600)

182.9
(600)

G

187-448
(X250-600)

187-448
(250-600)

18.3
(60)

53.3
(175)

114.3
(375)

manufacturer

for insulation

rating.

182.9
(600)

182.9
(600)

182.9
(600)

182.9
(600)

182.9
(600)

Type A Motor Characteristics:

No phase paper or misplaced phase paper, lower quality insulation systems, corona inception voltages between 850 and 1000 volts.

Type B Motor Characteristics:

Properly placed phase paper, medium quality insulation systems, corona inception voltages between 1000 and 1200 volts.

1329R Motors:

These AC Variable Speed motors are “Power Matched” for use with Allen-Bradley Drives. Each motor is energy efficient and
designed to meet or exceed the requirements of the Federal Energy Act of 1992. All 1329R motors are optimized for variable speed
operation and include premium inverter grade insulation systems which meet or exceed NEMA MG1. Part 31.40.4.2.