5–9

Programming

[Power OL Count]– Firmware 4.01 & later

Displays the percentage of accumulated I

2

t for the

drive thermal overload protection. Running
continuously above 115% of drive rated amps will
accumulate a value of 100% and generate an
Overtemp Fault (F08).

Parameter Number

84

Parameter Type

Read Only

Display Units / Drive Units

1 % / 4096 = 100%

Factory Default

None

Minimum Value

0%

Maximum Value

200%

[Motor OL Count]– Firmware 4.01 & later

This parameter displays the percentage of
accumulated I

2

t for the motor overload protection.

Running continuously at programmed [Overload
Amps] will accumulate approximately 70%.
Reduction of load will reduce the OL count. 100%
value will generate an Overload Fault (F07).

Parameter Number

202

Parameter Type

Read Only

Display Units / Drive Units

1 % / 4096 = 100%

Factory Default

None

Minimum Value

0%

Maximum Value

200%

[Last Fault]

This parameter displays the last drive fault. It is
updated whenever a new fault occurs.

Parameter Number

4

Parameter Type

Read Only

Display Units / Drive Units

Fault Number / Fault Number

Factory Default

None

Minimum Value

None

Maximum Value

None

[Torque Current]

This parameter displays the amount of current that
is in phase with the fundamental voltage component.
It is the current that is actually producing torque.

Parameter Number

162

Parameter Type

Read Only

Display Units / Drive Units

0.1 Amp / 4096 = Rated Amps (Motoring)

Factory Default

None

Minimum Value

–200% Drive Rating

Maximum Value

+200% Drive Rating

[Flux Current]

This parameter displays the amount of current that
is out of phase with the fundamental voltage
component. It is the current required to maintain
motor flux.

Parameter Number

163

Parameter Type

Read Only

Display Units / Drive Units

0.1 Amp / 4096 = Rated Amps (Motoring)

Factory Default

None

Minimum Value

–200% Drive Rating

Maximum Value

+200% Drive Rating

[% Output Power]

This parameter displays the % output power of the
drive.

Parameter Number

3

Parameter Type

Read Only

Display Units / Drive Units

1 % /

±

4096 =

±

100%

Factory Default

None

Minimum Value

–200% Drive Rated Output Power

Maximum Value

+200% Drive Rated Output Power

[% Output Curr]

This parameter displays the % output current of the
drive.

Parameter Number

2

Parameter Type

Read Only

Display Units / Drive Units

1 % / 4096 = 100%

Factory Default

None

Minimum Value

0%

Maximum Value

200% Rated Drive Output Current