Alarms – Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual

Page 140

Advertising
background image

6–8

Troubleshooting

Table 6.C presents a listing and description of the drive alarms.
Alarm status can be viewed by selecting the [Drive Alarm]
parameter. An active alarm will be indicated by its corresponding bit
being set to high (1). Any high bit (1) will energize CR4 (see
figure 2.3).

Parameter Number

60

Parameter Type

Read Only

Bus Charging

Regenerating Current Limit

Regenerating Voltage Limit

Line Loss In Progress

Motor Stalled

Ground Warning

Bit 15

Bit 13 Bit 12 Bit 11 Bit 10 Bit 9

Bit 8

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Mtr Overload

Unused

Bit 14

Hardware Current Limit

Motoring Current Limit

Motor OL Trip

Auto Reset

Voltage Check

Heatsink Temp

Auxiliary Input

4-20 mA Loss

Table 6.C
Alarm Conditions

Alarm Name

Description

Bus Charging

Precharge of DC bus capacitors is in progress.

Hardware Current Limit

An alarm will be issued when 220% of drive rated current is
reached.

Motoring Current Limit

The value programmed for [Current Limit] has been
exceeded while in the motoring mode.

Regenerating Current Limit

An alarm will be issued when the value set for [Current
Limit] has been exceeded while the motor is regenerating.

Regenerating Voltage Limit

Bus limiting is active.

Line Loss In Progress

An alarm will be issued when the AC incoming voltage
drops below 20% of input or a 150 volt drop takes place.

Mtr Overload

At the present value of output amps, a motor overload trip
will eventually occur.

Motor Stalled

The drive output frequency folds to 0 Hz and current limit is
still active or voltage limit will not allow decel.

Ground Warning

Ground current exceeds 2 amperes.

Auxiliary Input

TB3 terminal 24 circuit is open.

Heatsink Temp

Temperature of drive heatsink has exceeded its limit.

Voltage Check

Voltage at drive output terminals is equal to, or greater than
10% of drive rated volts (i.e. 46V for 460V drive) when
Start command is issued and flying start is disabled. Drive
will not start until terminal voltage falls below 10% of drive
rating or flying start is enabled.

4-20mA Loss

4-20mA signal lost.

Motor OL Trip

This bit will be high when the motor overload function has
integrated high enough to cause a motor overload fault.
This bit is active regardless of the [Motor Overload] state
(enabled/disabled).

Auto Reset

Drive is attempting to reset a fault using [Reset/Run Tries]
& [Reset/Run Time].

Alarms

Advertising