Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual
Page 77
4–13
Start-Up
or
Set Power-Up Display
25. With HIM software versions 2.02 & up,
the power-up display (Status, Process or
Password) can be programmed to appear
when drive power is applied. Simply
access the desired display and
simultaneously press the Increment and
Decrement keys.
Set Electronic Overload
26. Electronic overload protection is factory
set to drive maximum.
A. To properly set the electronic overload
protection, program [Overload Amps]
(Setup group) to the actual nameplate
F.L.A.
B. If the motor speed range is greater than
2:1, program [Overload Mode] to the
proper derate.
For the typical steps involved when
programming, refer to step 20.
27. This completes the basic start-up
procedure. Depending on your application,
further parameter programming may be
required. Refer to Chapter 5 for
information.
28. If password protection is enabled, log out
as described in Chapter 3.