C–4

CE Conformity

1336 PLUS

Frames A1 - A4

2

1336 PLUS & FORCE

Frames B & C

2

To Motor

1

Cable Supplied with Filter

1

Conduit

1

To Motor

1

Three-Phase Input

1

Access

Panel

Flat Washer

Star Washers

Bolt

Bolt

Important: Drive and filter must be
mounted to a common back plane
with a positive electrical bond and
in close proximity to one another.

Important: A positive electrical bond must
be maintained between drive and filter at
all 4 corners. Star washers can be
eliminated if a positive electrical
bond is assured.

Three-Phase

Input

1

1

Input power (source to filter) and output power (filter to drive and drive to motor) wiring must be in conduit or have shielding/armor with equivalent attenuation.
Shielding/armor must be bonded to the metal bottom plate. See requirements 6 & 7 on page C–1.

2

Refer to the Filter Selection table on page C–2 for frame references and corresponding catalog numbers.