Run/accel boost] – firmware below 4.01, Pwm frequency, Analog invert] – firmware below 4.01 – Rockwell Automation 1336S Plus FRN 1.xx-5.xx User Manual

Page 93: Analog invert, Analog trim en

Advertising
background image

5–15

Programming

[Run/Accel Boost] – Firmware below 4.01

Sets the percentage of Auto Boost that is applied to
the motor during constant speed or decel. If Auto
Boost is selected in the [DC Boost Select]
parameter (see preceding page), boost is applied as
shown in the adjacent chart.

Parameter Number

169

Parameter Type

Read and Write

Display Units / Drive Units

1%

Factory Default

100%

Minimum Value

0%

Maximum Value

100%

Drive Mode

Auto Boost Applied

Accelerating

Programmed Auto Boost %

Constant Speed

Programmed Auto Boost % x [Run/Accel Boost]

Decelerating

Programmed Auto Boost % x [Run/Accel Boost]

[PWM Frequency]

This parameter sets the carrier frequency for the
sine coded PWM output waveform.

This parameter cannot be changed while the drive is
running.

Refer to page 1–1 for Frame Reference information
and the Derating Guidelines in Appendix A.

Parameter Number

45

Parameter Type

Read and Write

Display Units / Drive Units

2 KHz / KHz/2

Factory Default

Based on drive type

Minimum Value

2 KHz

Maximum Value

A Frame Drives = 10 kHz
B Frame Drives = 8 kHz

C Frame Drives & Up = 6 kHz

[Analog Invert] – Firmware below 4.01

This parameter enables the inverting function for the
analog input signal at TB2.

This parameter cannot be changed while the drive is
running.

Parameter Number

84

Parameter Type

Read and Write

Factory Default

“Disabled”

Units

Display Drive

“Disabled” 0

“Enabled” 1

Analog Invert

Drive Output

Frequency

Maximum

Speed

Minimum

Frequency

0

V

4 mA

10

V

20

mA

Disab

led

Ena

bled

Analog Input Signal

[Analog Trim En]

This parameter enables the pot terminals at TB2,
terminals 1, 2 & 3 as a trim function to the analog
inputs at TB2 terminals 4 & 5 or 4 & 6. A 10k ohm
pot provides a trim range of approximately 10% of
[Maximum Freq]. Drive status must be “Stopped”
before programming changes will take effect.

Parameter Number

90

Parameter Type

Read and Write

Factory Default

“Disabled”

Units

Display Drive

“Disabled” 0

“Enabled” 1

Advanced Setup